Available control settings and system presets

Evergreen control settings available in BASIC MODE (see Advanced Manual for ADVANCED MODE settings)
Boiler Model
Control Type
High Altitude
LP Gas
ODT Sensor Exempt
Manual Reset High Limit Temp
WWSD Temp
Adjust Outdoor
Circulator Exercising
Freeze Protect Circs
Reset Factory Default
Inputs Assigned (non-selectable)
System Type
Target Mod Sensor (non-selectable)
Target Adjust (non-selectable)
Supply Max
Supply Min (not available for DHW) *
OD Reset Max (or Volts for Max) *
OD Reset Min (or Volts for Min) *
Boost Time *
System types available in BASIC MODE (each option shown with factory settings)
8-Character
Abbreviation
Fan-coil
FAN-COIL
Finned Tube Baseboard
FIN BASE
Cast Iron Baseboard
IRONBASE
Cast Iron Radiators
RADIATOR
Radiant - slab on grade
RAD SLAB
Radiant - thin slab
RAD SLAB
Radiant - below floor
RADFLOOR
(staple up)
Radiant - above floor
RADFLOOR
(sleeper system)
Domestic Hot Water
DOMESTIC
XXXXXXXX
Custom (user defined)
(user input)
– 72 –
-
FIRED WATER BOILER
Inputs Assigned (non-selectable)
System Type
Target Mod Sensor (non-selectable)
Target Adjust (non-selectable)
Supply Max
Supply Min (not available for DHW) *
OD Reset Max (or Volts for Max) *
OD Reset Min (or Volts for Min) *
Boost Time *
Inputs Assigned (non-selectable)
System Type
Target Mod Sensor (non-selectable)
Target Adjust (non-selectable)
Supply Max
Supply Min (not available for DHW) *
OD Reset Max (or Volts for Max) *
OD Reset Min (or Volts for Min) *
Boost Time *
3-Character
Supply Max
Abbreviation
FCL
FTB
CIB
CIR
RSG
RTS
RSU
RAF
DHW
first three of
user input
— Boiler Manual
* These items only appear in the menus if Target Adjust is active.
OD Reset
Supply
°F
Min °F
Min °F
180
0
140
180
0
130
180
0
120
180
0
120
120
0
80
140
0
80
160
0
90
140
0
90
180
N/A
N/A
180
0
70
Priority 1, 2 or 3
Source (TT1 or 0-10v)
AUX PUMP/OUTPUT
Off
Priority 1, 2 or 3
AUX PUMP/OUTPUT
Off
See Figure 77, page 78 for details.
See Figure 82, page 83 for details.
See Figure 82, page 83 for details.
OD Reset
Run
Max °F
Boiler Pump
70
YES
70
YES
70
YES
70
YES
70
YES
70
YES
70
YES
70
YES
N/A
NO
70
YES
Part number 550-100-131/0715
Run AUX
PUMP/
OUTPUT
YES
YES
YES
YES
YES
YES
YES
YES
NO
YES