ECO
®
Tec
series 2 gas-fired water boiler – boiler manual
Available control settings and system presets
ECO Tec
Figure 102
Control / Priority settings
PRIORITY SETTINGS
PARAMETER NAME
•
ASSIGNED INPUTS
•
SYSTEM TYPE
•
TARGET MODULATION SENSOR
•
TARGET ADJUST
•
MAX TARGET TEMP
• HOT WATER TEMP (COMBI ONLY)
• MIN TARGET TEMP
•
COMBI ENABLED (COMBI ONLY)
•
OUTDOOR TEMP FOR MIN TARGET
•
OUTDOOR TEMP FOR MAX TARGET
•
VOLTAGE FOR MAX TARGET
(TARGET ADJUST)
•
VOLTAGE FOR MIN TARGET
(TARGET ADJUST)
•
TARGET BOOST TIME
•
SYSTEM SUPPLY OFF DIFF
•
DHW OFF DIFF
•
SYSTEM SUPPLY ON DIFF
•
DHW ON DIFF
•
MAX BOILER TEMP
•
BOILER OUT OFF DIFF
•
BOILER OUT ON DIFF
•
COLD START ERROR
•
MAX ON TIME
•
MIN ON TIME
•
PREHEAT MODE (COMBI ONLY)
•
PREHEAT TEMP (COMBI ONLY)
• PREHEAT CIRC DIFF (COMBI ONLY)
• PREHEAT ON DIFF (COMBI ONLY)
• PREHEAT OFF DIFF (COMBI ONLY)
• ECO BOOST (COMBI ONLY)
• ECO BOOST SETPOINT (COMBI ONLY)
• ECO BOOST ON DIFF (COMBI ONLY)
112
Range/
options
1, 2, 3, 4, 0-10V, FLOW
See System Type Presets
SYSTEM SUPPLY,
SYSTEM SUPPLY if
BOILER OUT, DHW
detected, Boiler Out
OUT
Outdoor Temp, 0-10V,
Outdoor Temp (If
none
See System Type Presets
See System Type Presets
See System Type Presets
ON, OFF
50 - 100
-20 to 49
5.0 - 10.0
0.0 - 4.9
OFF, 1 - 240
5 - 15
1 - 20
5 - 30
1 - 20
60-185
2 - 15
2 - 30
0 - 150
OFF, 1 - 240
OFF, 1 - 240
OFF, Economy,
High Performance
70 - 180
1 - 30
1 - 30
1 - 30
OFF, ON
70 - 180
1 - 30
Default
setting
-
OFF
COMBI DHW
if not
attached)
See System Type
Presets
N/A
See System Type
Presets
N/A
70
0
10.0
0.0
OFF
10
N/A
10
N/A
Varies with
System Type
5
5
50
30
15
N/A
N/A
120 (Econ), 140 (H. Perf)
N/A
30 (Econ), 10 (H. Perf)
N/A
10 (Econ), 5 (H. Perf)
N/A
N/A
N/A
N/A
COMBI
UNITS
default
FLOW
-
-
DHW OUT
-
None
-
°F
N/A
120
°F
N/A
°F
ON
-
N/A
°F
N/A
°F
N/A
V
N/A
V
N/A
M
N/A
°F
10
°F
N/A
°F
1
°F
180
°F
5
°F
5
°F
N/A
°F
60
M
N/A
M
Economy
-
°F
°F
°F
10
°F
ON
-
130
°F
10
°F
Part number 550-100-270/0122