CHASE INSTALLATIONS
Instructions for chase installations are included with the chase style
termination chosen. In a multiple chase installation, be sure to provide
adequate distance between terminations to prevent smoke spillage
from one termination to another. We suggest that terminations be
separated at least 24", center to center and stacked at a vertical height
difference of 18" (see Figure 16).
Note: If a decorative shroud is to be installed, contact the manufac-
turer for specifications.
10 FOOT RULE
All flue gas outlet chimney terminations must extend a minimum of
3 feet in height above the highest point where it passes through the
roof and must be at least 2 feet above the highest point of the roof
that is within a horizontal distance of 10 feet (see Figure 17).
FINISHING FIREPLACE
Combustible materials, such as wallboard, gypsum board, sheet rock,
drywall, plywood, etc. may make direct contact with sides and top
around the fireplace face. It is important that combustible materials
do not overlap the face itself. Brick, glass, tile or other noncombustible
materials may overlap the front face provided they do not obstruct
essential openings like louvered slots or any other opening. When
overlapping with a noncombustible facing material, use only noncom-
bustible mortar or adhesive.
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
Overlap
Shingles Top
and Sides
Figure 15 - Termination
127020-01C
VENTING INSTALLATION Continued
RTL-8DM
Level of
Flue Gas
Outlet
Caulk
Collar
Flashing
Underlap
Shingles
Bottom Only
EFFECTIVE HEIGHT
OF TERMINATION CAP
14.5 FT.
14.5 FT.
MINIMUM
MINIMUM
HEIGHT
HEIGHT
Superiorfireplaces.US.com
24" Min.
24" Min.
Figure 16 - Multiple Chase Installation
10'
2' Min.
Figure 17 - 10 Foot Rule
EFFECTIVE HEIGHT
OF TERMINATION CAP
UP TO
6FT. MAX.
Figure 18 - Typical Residential Installations
18"
Min.
Typ.
Level of
Flue Gas
Outlet
10'
3' Min.
2' Min.
3' Min.
EFFECTIVE HEIGHT
EFFECTIVE HEIGHT
OF TERMINATION CAP
OF TERMINATION CAP
MIN. HEIGHT
OF 22 FT. (WITH
2 ELBOW SETS)
MAX. HEIGHT OF
50 FT.
MAX. HEIGHT
50 FT.
(ANY SYSTEM)
UP TO
6FT. MAX.
30E-8DM
30E-8DM
11