Condenser high temperature protection (only for heat pump)
7.7 Dehumidifying mode
Indoor fan speed at low speed.
Protection is same as cooling mode.
7.8 Heating mode
7.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve must delay 2
minutes compared with compressor if the compressor changed into non-heating mode or turned off. 4-way valve doesn't
delay in dehumidifying mode.
7.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except for the defrosting
mode or the end of defrost.
7.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes after starting and
then judge temperature. Meanwhile other protections are still valid.
* This parameter can be changed from 0 to 3