300 min
Terminal
Assembly
Top View Rear Flue
Fig. 9
Plume
Displacement
Kit
Air Inlet
Fig. 10
7219706 - 01 (04/15)
*
Property Boundary Line
Opening
Window or Door
150mm
MIN.
Under car ports we recommend the use of the plume
displacement kit. The terminal position must ensure the
safe and nuisance - free dispersal of combustion
products.
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance and
that the terminal will not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access, then a
suitable terminal guard must be provided.
*4. Reduction to the boundary is possible down to 25mm but
the flue deflector must be used (see 5.3.12).
The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than
300mm in accordance with the diagram opposite
(Fig. 9).
If fitting a Plume Displacement Flue Kit, the air inlet
must be a minimum of 150mm from any opening
windows or doors (see Fig. 10).
The Plume Displacement flue gas discharge terminal
and air inlet must always terminate in the same
pressure zone i.e. on the same facing wall.
Before Installation
5
EcoBlue Plus Combi
33