Outdoor Temperature Sensor (Optional) - Navien NCB-24LSWE Installation & Operation Manual

Condensing combi boiler
Hide thumbs Also See for NCB-24LSWE:
Table of Contents

Advertisement

10.5 Outdoor Temperature Sensor (Optional)

Outdoor Temperature Sensor Installation
1. Pull out the sensor body from the cap.
2. Attach the body to the wall using the screws/anchors provided with the device.
3. Run the wires into the device body through the grommet opening.
4. Connect the wires to the terminal block.
5. Attach the cap to the body.
Navien Outdoor Temperature Sensor
Outdoor Temperature Sensor Installation Guidelines
Avoid areas with temperature fluctuations by direct sunlight, and where the temperature may not be representative of true outdoor
temperature.
Best location to install the temperature sensor is on a North or Northeast side of a structure under eaves where the sensor is shielded
from direct sunlight.
Avoid placing sensor in close proximity of heat sources that may affect correct temperature sensing. (fans, exhausts, vents, lights)
Avoid installing the sensor in areas where the sensor is subjected to excessive moisture.
Use 18 gauge wiring (thermostat wiring) with no splices. (except at the unit harness connection with yellow leader wire.)
Caution should be taken to avoid potential electromagnetic interference (EMI) by routing separately from potential sources such as line
voltage wiring. When necessary, shielded cable may be used.
Make sure wiring connections are secure before closing the cap.
The sensor is a water resistant device.
Any damage to the device may require the replacement of the entire component.
62
Appendixes

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ncb-34lsweNcb-28lsweNcb-40lswe

Table of Contents