16
Horizontal Termination with Two Elbows
(
one 90° vertical and one 90° or 45° horizontal elbow
•
If using a Snorkel Termination (14" or 36") add the snorkel height to the vertical height (snorkel
terminations are used primarily for basement installations).
•
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.
19' max (5.8m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
© Travis Industries
Installation
NOTE:
Horizontal sections require a 1/4" (0.250mm)
rise every 12" (305mm) of travel.
NATURAL GAS: Min. 2' (0.61m) Section Required
PROPANE (LP): Min. 3' (0.915m) Section Required
(for qualified installers only)
Restrictor
Position # 5
NOTE:
Restrictor positions are based upon lab
tests. The ideal restrictor position may vary
Restrictor
Position # 1
slightly, especially when the termination is
near a demarkation line.
4090717
)
100-01225_000
19' max (5.8m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet