CIRCUIT BREAKER AND FUSED DISCONNECT SWITCH SIZES
kW
VOLTS
PH
6
208
1
208
3
240
1
240
3
480
3
9
208
1
208
3
240
1
240
3
480
3
12
208
1
208
3
240
1
240
3
480
3
15
208
1
208
3
240
1
240
3
480
3
18
208
1
208
3
240
1
240
3
480
3
24
208
1
208
3
240
1
240
3
480
3
30
208
1
208
3
240
1
240
3
480
3
36
208
1
208
3
240
1
240
3
480
3
45
208
3
240
1
240
3
480
3
54
208
3
240
3
480
3
58
208
3
240
3
480
3
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers are to be mounted remotely and wired by the contractor. Sizes are
based on the NEC table 310-16. Conduit size is based on conductors plus ground wire sizing as per NEC table 250-122.
L1
L2
L3
29
29
—
14
25
14
25
25
—
13
22
13
6
11
6
43
43
—
22
38
22
38
38
—
19
33
19
9
16
9
58
58
—
33
33
33
50
50
—
29
29
29
14
14
14
72
72
—
42
42
42
63
63
—
36
36
36
18
18
18
87
87
—
48
48
48
75
75
—
43
43
43
22
22
22
115
115
—
67
67
67
100
100
—
58
58
58
30
30
30
144
144
—
83
83
83
125
125
—
72
72
72
36
36
36
173
173
—
100
100
100
150
150
—
87
87
87
43
43
43
125
125
125
188
188
—
108
108
108
54
54
54
150
150
150
130
130
130
65
65
65
162
162
162
141
141
141
71
71
71
Breaker or Fuse Size Copper Wire Size
40
40
40
30
15
60
50
50
50
20
90
50
70
40
20
90
60
90
50
30
125
60
100
60
30
150
90
125
90
40
200
125
175
100
50
225
125
200
125
60
175
250
150
70
200
175
90
225
200
90
7
Conduit Size
8
8
8
10
14
6
8
8
8
12
3
8
4
8
12
3
6
3
8
10
1
1-1/4"
6
3
6
10
1/0
1-1/4"
3
1-1/4"
1
1-1/4"
3
1-1/4"
8
3/0
1-1/2"
3
1-1/2"
2/0
1-1/2"
3
1-1/4"
8
4/0
1
1-1/2"
3/0
1-1/2"
1
1-1/2"
6
2/0
250 MCM
1/0
1-1/2"
4
3/0
1-1/2"
2/0
3
1-1/4"
4/0
3/0
1-1/2"
3
1-1/4"
1/2"
3/4"
1/2"
1/2"
1/2"
3/4"
3/4"
1/2"
3/4"
1/2"
1"
3/4"
1"
3/4"
1/2"
1"
3/4"
1"
3/4"
1/2"
3/4"
1"
3/4"
1/2"
3/4"
3/4"
2"
3/4"
2"
2"
1"
2"
2"