Features

Power Module

E
B
G
F
D
C
Power Module Rear Panel with Detachable PDU
A
Battery Pack Connector: Insert the external battery pack's
male battery connector into this female battery connector.
Remove the cover (not shown) for access.
B
Accessory Card Slot: Remove the cover to install optional
accessory cards that provide the UPS system with additional
functionality.
The
(SNMPWEBCARD) goes in this slot to provide remote
monitoring and control via SNMP, Web or telnet. Connect an
optional environmental sensor (ENVIROSENSE) to monitor
temperature
and
(RELAYIOCARD) and MODBUS (MODBUSCARD) cards
are also available.
C
USB Port: The USB port may be used to connect your UPS to
a workstation or server. It is used with Tripp Lite software and
the included USB cable to monitor and manage the UPS
remotely over a network and to automatically save open files
and shut down equipment during a blackout. For USB
communications, both DIP switches must be in the DOWN
position. This will disable the RS-232 port. See Optional
Connections section for more information.
D
Port Selection DIP Switches: When the DIP switches are both
down, the USB port is active. When the DIP switches are both
up, the RS-232 port is active.
201102089 93-2982.indb 6
continued
H
(Shown without wiring harness.)
UPS
network
management
humidity.
Dry
contact
A
E
RS-232 Serial Port (DB9): Connect this port to a computer
with the included DB9 cable to allow the computer and UPS
system to communicate. Make sure DIP switches of USB port
module are both set to the UP position. This disables the USB
port. See Optional Connection section for more information.
F
EPO (Emergency Power Off) Port: Use the included EPO
card
cable to connect this port to a user-supplied EPO switch to
enable emergency shutdown. Do not connect this port to a
telephone line. See Optional Connection section for more
closure
information.
G
Parallel: This port allows 2 identical power modules to operate
in parallel when used in conjunction with a parallel PDU. Do
not connect anything to this port unless the UPS system will be
operating in a parallel configuration.
H
Exhaust Fan: The fan cools the power module.
Wiring Harness (not shown): The wiring harness comes pre-
installed to the PDU. It guides and protects the wiring that connects
the power module's input and output terminals to the corresponding
terminals on the Transformer. Note: The harness is pre-installed to
the PDU, but must be hardwired to the Transformer.
6
Detachable Hardwire PDU