band to seal it to outer pipe.
For OEM factory installation, the round top termina-
tion may be site installed. Protect exposed pipe from
adverse weather during transit.
Slide the telescoping pipes of the unitized SKC8-MH
Chimney Top into their respective chimney pipe section.
The flue section telescopes inwardly. The outer section
telescopes over the outer pipe. (Fig. 19)
Using the holes in the outer sections as guides, drill
three (3) 1/8" holes into the outer pipe. Fasten the
body assembly to the outer pipe with the #10 x 1/2 inch
Chimney Top
#10 x 1/2"
Screws
Intermediate
Section
Fig. 19 Assembly of Mobile Home Chimney Top.
screws provided.
Finishing
CAUTION: All joints between the finished wall and
the fireplace surround (top/sides) must be sealed with
noncombustible material to prevent cold air leakage into
the room. Only noncombustible material may be applied
Finish Wall
Finish the wall with material of your choice. Do not
install a combustible mantel shelf less than 12"
(305 mm) from top of grille opening for circulating
models. Do not install a mantel face plate less than
3" (76 mm) from top of grille opening for circulating
models. (Fig. 20) If a combustible material is used be-
low a flat mantel shelf, consult your local building codes
for minimum clearance from top of fireplace opening to
bottom of mantel shelf.
All joints (top, bottom and sides) where wall or decora-
tive facing material meets fireplace surround must be
completely sealed with a noncombustible material. (Fig.
20 or 21)
7412972
MH107
MH107
chimney top
6/2/99 djt
BC36MH, BC42MH Woodburning Fireplace
Combustible Man-
tel and Trim
12" (305 mm)
Min.
Side View
Must be sealed with non-
Fireplace
combustible material
Front
Fig. 20 Fireplace surround flush with finished wall.
NOTE: No side wall protection is required for fireplaces
installed at 45° to two (2) side walls (corner installation).
FP531b
Side Wall Protection
mantel clearances
9/03 djt
Adjacent combustible side walls that are within the
minimum dimensions shown in Figure 21 of fireplace
opening must be protected with Vermont Castings
Group Wall Shield Model SP40 or a specially built wall
shield described below.
The special wall shield design described in Figure 14 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must = 1.85
minimum.
Examples of wall shield insulation:
1. Manville - CERAFORM 126, K = .27, 1/2 inches
thick.
2. Vermont Castings Group - EH2416, K = .458, 1
inch thick required.
12"
(305 mm)
Finished Wall
Max.
1 "
Header
(38 mm)
Standoff
Noncombustible
3"
Material
(76 mm)
Min.
Grille Open-
ing
Fireplace Front
"
2 x 4 Stud
Finished Wall
FP531b
13