Trane TCONT800AS11AA Installation Instructions Manual page 8

Touch screen programmable comfort control
Table of Contents

Advertisement

TCONT800AS11AA TOUCH SCREEN PROGRAMMABLE COMFORT CONTROL
Installer
Setup
Select
Number
Continuous
0280
Backlight
Changeover
0300
Deadband
0310
Temperature
0320
Indication
Scale
Daylight
0330
Savings
Remote
0340
Temperature
Sensor
(Outdoor or
Indoor)
Furnace Filter
0500
Change
Reminder
Humidifier
0510
Pad
Replacement
Reminder
Adaptive
0530
Intelligent
Recovery™
Pub. No. 18-HD25D18-3
69-1787—03
Table 4. Installer Setup Menu. (Continued)
Factory Setting
Option
Description
0
Backlight not on
continuously.
Comfort control
backlight comes
on with each key
press.
0
Manual changeover 1
3
Heating and cooling
setpoints can be set
no closer than
3°F (1.5°C)
0
Temperature is
displayed in °F.
1
Daylight savings
enabled (use
through 2006 and
for areas that do not
use the new 2007
DST calendar).
0
No remote
temperature sensor
0
Furnace filter
change reminder off
0
Humidifier pad
replacement
reminder off
1
Adaptive Intelligent
Recovery™ control
is activated (system
starts early so
setpoint is reached
by start of program
period).
Other Choices
Options
Description
1
Backlight is on continuously
(comfort control must have a
common wire attached for
this function).
1—auto changeover
2 thru 9
Heating and cooling
setpoints can be set no
closer than chosen
value:
2—2°F (1°C)
3—3°F (2°C)
4—4°F (2.5°C)
5—5°F (3°C)
6—6°F (3.5°C)
7—7°F (4°C)
8—8°F (4.5°C)
9—9°F (5°C)
1
Temperature is displayed
in °C.
0,2
0—Daylight savings is
disabled.
2—Daylight savings is
enabled (start using in 2007,
for areas that use the new
2007 DST calendar).
1,3
1—outdoor temperature
sensor for display only.
3—indoor temperature
sensor.
1-6
1—10 run time days
2—30 run time days
3—60 run time days
4—90 run time days
5—120 run time days
6—365 run time days
1-3
1—90 calendar days
2—180 calendar days
3—365 calendar days
0
0—conventional recovery
(system starts recovery at
programmed time)
8
Comments
Option is always
shown; however,
continuously on
backlight works
only if comfort
control is wired
with 24 Vac
Common.
Shown only if
automatic
changeover is
selected.
Set to 0 in areas
that do not follow
daylight savings.
Defaults and
Options depend
on System Type
selected. Indoor
Temperature
Sensor uses an
averaging
network and does
not include on-
board sensor.
Run time based
on call for fan.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

18-hd25d18-3

Table of Contents