Refrigeration - Remote Condenser Models - Scotsman F0522 Installation And User Manual

Modular flaked and nugget/ prodigy plus d series
Table of Contents

Advertisement

N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual

Refrigeration - Remote Condenser Models

Junction
Box
Cover
Ground Wire
Connection
Install
Black
Strain
White
Relief
Ground
Install
Strain
Relief
Ground Wire
Connection
Install
Strain
Relief
Power
Supply
Wires
Condenser
Fan Motor
Blue
Junction
Box
Cover
Power
Black
Supply
White
Wires
Ground
Remote condenser models have additional installation
needs.
The correct remote condenser fan and coil must
be connected to the ice making head. Liquid and
discharge tubing connections are on the back of the
ice machine cabinet. Pre-charged tubing kits are
available in several lengths to accommodate most
installations. Order the one that just exceeds the
length needed for the installation.
The kit numbers are:
• RTE10
• RTE25
• RTE40
• RTE75
There are limits as to how far away from the ice
machine and where the remote condenser can be
located. See page 10 for those limits.
The correct condenser must be used.
Ice Machine
Model
F0822R,
N0622R
F1222R,
N0922R
N1322R
Do not reuse condenser coils contaminated with
mineral oil (used with R-502 for example). They will
cause compressor failure and will void the warranty.
A headmaster is required for all remote condenser
systems. Prior condensers did not have a
headmaster. New head / prior condenser retrofits can
use headmaster kit KPFHM.
Use of non-Scotsman condensers requires pre-
approval from Scotsman Engineering.
October 2014
Page 9
Voltage
Condenser
Model
115
ERC111-1
208-230
ERC311-32
208-230
ERC311-32