A-7
2. Take necessary steps to assure load is limited to the capacity
of the Vantage by installing a 50 amp, 240 VAC double pole
circuit breaker. Maximum rated load for each leg of the 240
VAC auxiliary is 50 amps. Loading above the rated output will
reduce output voltage below the allowable -10% of rated
voltage which may damage appliances or other motor-driven
equipment and may result in overheating of the Vantage
engine.
Figure A.2 Connection of the Vantage to Premises Wiring
POWER
240 Volt
60 Hz.
COMPANY
3-Wire
Service
METER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
INSTALLATION
240 VOLT
120 VOLT
120 VOLT
50AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
240 VOLT
BREAKER
GND
Vantage 500 CUMMINS
3. Install a 50 amp 120/240 VAC plug (NEMA Type 14-50) to the
double-pole circuit breaker using No. 6, 4 conductor cable of
the desired length. (The 50 amp, 120/240 VAC plug is
available in the optional K802R plug kit.)
4. Plug this cable into the 50 Amp 120/240 Volt receptacle on the
Vantage case front.
GROUNDED CONDUCTOR
GROUND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
A-7
NEUTRAL
BUS
N
LOAD
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION