FUNCTION SETTING

11-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions are available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
Function
Power failure
OFF
automatic recovery
ON
Indoor temperature
Average data from each indoor unit
detecting *
Data from the indoor unit with remote controller
Data from main remote controller
LOSSNAY
Not supported
connectivity
Supported (Indoor unit does not intake outdoor air through LOSSNAY)
Supported (Indoor unit intakes outdoor air through LOSSNAY)
Power supply
240V
voltage
220V, 230V
Frost prevention
2: (Normal)
temperature
3:
Humidifier control
When the compressor operates, the humidifier also operates.
(Heating mode)
When the fan operates, the humidifier also operates.
Change of defrosting
Standard
control
For high humidity
Refrigerant leakage
80%
setting (%)
60%
* The functions above are available only when the wired remote controller is used. The functions are not available for floor
standing models.
Meaning of "Function setting"
Mode02:indoor temperature detecting
No. Indoor temperature(ta)=
No.1 Average data of the
Initial
sensor on all the
setting
indoor units
No.2 Data of the sensor
on the indoor unit that
connected
with remote controller
No.3 Data of the sensor
on main remote
controller.
OCH526B
Settings
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
ta=(A+B)/2
ta=(A+B)/2
ta=A
ta=B
ta=C
ta=C
Mode No. Setting No.
1
01
2
1
2
02
3
1
2
03
3
1
04
2
1
15
2
1
16
2
1
17
2
1
21
2
OUTDOOR
OUTDOOR
INDOOR
INDOOR
INDOOR
REMOTE
REMOTE
REMOTE
(MAIN)
(SUB)
(MAIN)
ta=A
ta=A
ta=C
82
: Initial setting
Remarks
(when sent from the factory)
The setting is
applied to all
the units in the
same
refrigerant
system.
OUTDOOR
INDOOR
REMOTE
REMOTE
(SUB)
(MAIN)
ta=A
ta=A
ta=C