Refrigerant System Diagram - Mitsubishi Mr.Slim PUHZ-SHW80VHA Service Manual

Split-type, heat pump air conditioners
Table of Contents

Advertisement

9

REFRIGERANT SYSTEM DIAGRAM

PUHZ-SHW80VHA
PUHZ-SHW80VHAR2(-BS).UK
PUHZ-SHW112YHA
PUHZ-SHW112YHAR1
PUHZ-SHW112YHAR2(-BS).UK PUHZ-SHW140YHAR2(-BS).UK
Ball valve
Refrigerant
GAS pipe
Strainer
connection
#50
(5/8 inch)
Charge plug
(Low pressure)
Strainer
#100
LEV-B
Refrigerant
LIQUID pipe
Strainer
connection
#100
(3/8 inch)
Stop valve
(with service port)
Symbol
Parts name
COMP
Compressor
H/P SW
High pressure switch (63H)
L/P SW
Low pressure switch (63L)
REV/V
Reversing (4-way) valve (21S4)
Charge plug
Charge plug
P-Sensor
Pressure sensor (63HS)
LEV-A
Linear expansion valve -A
LEV-B
Linear expansion valve -B
LEV-C
Linear expansion valve -C
TH32
Suction temperature thermistor
Refrigerant leakage detection
TH33
(Ref. check) thermistor
TH3
Liquid temperature thermistor
TH4
Discharge temperature thermistor
TH6
2-phase pipe temperature thermistor
TH7
Ambient temperature thermistor
TH34
Comp. surface temperature thermistor For protection
Power Receiver Power Receiver
HIC
Heat interchange circuit
Plate HEX
Plate Heat Exchanger
TH1
Outlet water temperature thermistor
TH2
Liquid pipe temperature thermistor
OCH526B
PUHZ-SHW112VHA
PUHZ-SHW112VHAR2(-BS).UK
PUHZ-SHW140YHA
PUHZ-SHW140YHAR1
REV/N
Charge plug
(High pressure)
Muffler
L/P SW
Strainer
#100
Strainer
#100
COMP
Power
receiver
LEV-C
DC inverter scroll compressor (Mitsubishi Electric Corporation)
For protection (OFF: 4.15MPa)
For protection (OFF: -0.03MPa)
Change the refrigerant circuit (Heating / Cooling) and for Defrosting
High pressure / Low pressure / For production test use
For calculation of the condensing temperature from high pressure
Heating:Secondary LEV
Heating:Primary LEV
For HIC (heating only)
For LEV control
For refrigerant leakage detection
Heating:Evaporating temperature
For LEV control and for compressor protection
Outdoor 2-phase pipe temperature
For fan control and for compressor frequency control
For accumulation of refrigerant
For high heating capacity
MWA2-38PA (MITSUBISHI)
For fl ow temp. controller
For fl ow temp. controller
18
P-sensor
Heat exchanger
H/P SW
TH32
(Suction)
Strainer
#100
TH4
(Discharge)
TH34
(Comp. surface)
Injection port
HIC
Refrigerant flow in cooling
Refrigerant flow in heating
Detail
Cooling:Primary LEV
Cooling:Secondary LEV
Cooling:Sub cool liquid temperature
<Reference>
System example
TH7
(Ambient)
TH6
(2-phase pipe)
TH3
(Liquid)
Distributor
TH33
(Ref. check)
LEV-A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents