Soft Dry Operation; Forced Operation - LG Multi V CRUN Series Service Manual

Heat pump air conditioner
Hide thumbs Also See for Multi V CRUN Series:
Table of Contents

Advertisement

Soft Dry Operation

• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to
the cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room
temperature falls below compressor OFF temperature, Compressor OFF.
• In dehumidify mode, control of fan speed is as following.
Intake Air temperature
Setting temperature +1.0˚C
(Compressor ON)
Setting temperature
Setting temperature -0.5˚C
(Compressor OFF)
COMPRESSOR
OUTDOOR FAN
INDOOR FAN

Forced operation

• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• The standard conditions are as following.
Room Temperature
Operation Mode
FAN Speed
Setting Temperature
• Unit operates in low fan mode for first 15 seconds, then switched to proper operation mode according to
intake Air temperature.
Cooling
2min.58sec.
10min.
ON
OFF
ON
ON
OFF
ON
Selected
Fan
24°C
Cooling
High
22°C
Forced
Operation Button
R
7min.
10min.
Within 7min. Cooling
OFF
ON
OFF
OFF
ON
OFF
Low Fan
21°C Room Temperature 24°C
Soft Dry
Soft Dry Rule
Air Intake Temperature
Press the Forced Operation Button.
• Press the Forced Operation Button once
again to stop operation.
Operation Details
2min.58sec.
ON
OFF
ON
ON
OFF
ON
Selected
Low Fan
Fan
Room Temperature 21°C
Heating
High
24°C
Service Manual 65