LG Multi V CRUN Series Service Manual page 148

Heat pump air conditioner
Hide thumbs Also See for Multi V CRUN Series:
Table of Contents

Advertisement

Operation Dtails
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Intake Air Temperature
Setting Temperature +3°C
(Compressor OFF)
Setting Temperature
(Compressor ON)
INDOOR FAN
COMPRESSOR
• A point;
While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed,
when it becomes lower than 40˚C fan stops.
• B point;
When the indoor Heat-Exchanger temperature is higher than 42°C, fan operates at seleted fan
speed, when it becomes lower than 39°C, the fan operates at low speed.
Hot-Start Control
• The indoor fan stops until the evaporator piping temperature reaches 25°C.
• The operation diagram is as following.
148
Indoor Unit
minimum 3min
1min
Selecting
Hot Start
Low
Fan Speed
ON
PIPING
TEMPERATURE
25°C
22°C
INDOOR FAN
COMPRESSOR
: Selected Fan
A
minimum
10sec.
Low
OFF
Low
OFF
1min
ON
: Low Fan
: Fan Stop
B
minimum
10sec.
Selecting fan
Low
speed
ON
A
OFF
OFF