Checks; Flue Temperature Probe Ntc And Safety Thermal Fuse; Function; Removal - Biasi Activ A 12OV Service Manual

Wall hung, fan flue, room sealed, high efficiency gas boiler
Hide thumbs Also See for Activ A 12OV:
Table of Contents

Advertisement

13
Flue temperature probe NTC and
Safety thermal fuse
13.1

Function

The Flue temperature probe NTC A in Fig. 13.1 and
Fig. 13.2 senses the temperature of the combustion
products that flow through the condensing heat ex-
changer.
Fig. 13.1
If the temperature of the combustion products circuit
reaches the limit temperature, the Flue temperature
probe NTC reduces the gas flow rate to the burner. The
temperature of the combustion products should de-
crease to a safe value temperature.
In the case that the temperature of the combustion
products reaches a potentially dangerous value, it
stops the boiler operation (lock ---out).
This allows the use of plastic materials for the flue outlet
pipes and bends.
The use of kits different from the original isn't however
allowed, since the flue pipes are integral parts of the
boiler.
A
Fig. 13.2
A
B
13.2

Removal

Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1
Remove all the case panels.
2
Disconnect the connector B from the Flue tem-
perature probe NTC by pressing the plastic hook
placed on the side of the connector.
3
Unscrew and remove the flue temperature probe
A (Fig. 13.2) from the condensing heat ex-
changer.
4
Assemble the Flue temperature probe NTC carry-
ing out the removal operations in reverse se-
quence.
13.3

Checks

Overheat temperature value
n
1
Run the boiler and set the temperature at maxi-
mum by pressing the appropriate key.
2
Allow the boiler to reach its maximum operating
temperature. The boiler should maintain a tem-
perature below that of the Flue temperature
probe NTC and no overheat intervention should
occur.
Temperature---resistance relationship
n
1
Remove the Flue temperature probe NTC (see
section 13.2).
2
Measure the Flue temperature probe NTC electri-
cal resistance at the ambient temperature and
check it according to the graph in Fig. 13.3
Ω
12500
12000
11500
11000
10500
10000
9500
9000
8500
8000
7500
7000
6500
6000
5500
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Fig. 13.3
˚C
31