Fitting the test and control equipment
Note
Match or adjust the electrodes to the
switching points listed in the table.
The electrodes provided are matched at
the factory to the relevant boiler.
Boiler size
Permiss. operating pressure up to 13 bar
Reference
electrode to
low water
level
Dimension a
mm
1
502
2
527
3
540
4
551
5
585
6
608
7
618
8
622
9
625
Boiler size
Permiss. operating pressure from 16 bar
Reference
electrode to
low water
level
Dimension a
mm
1
492
2
517
3
530
4
541
5
575
6
598
7
608
8
612
9
615
14
(cont.)
In each connector, only one electrode
can be fitted for limiting the water level.
However, the water level controller and
limiter can be combined.
Ensure the electrodes of multi boiler sys-
tems are not interchanged.
Pump on
Pump off
Dimension b
Dimension c
mm
mm
462
422
487
447
500
460
511
471
545
505
568
528
578
538
582
542
585
545
Pump on
Pump off
Dimension b
Dimension c
mm
mm
452
412
477
437
490
450
501
461
535
495
558
518
568
528
572
532
575
535
Maximum
water level
HW
Dimension d
mm
357
382
395
406
440
463
473
477
480
Maximum
water level
HW
Dimension d
mm
357
382
395
406
440
463
473
477
480