Date
This is the system's real-time date setting. The system control program sends to each module the date
entered at the System Control Cabinet (SCC). You cannot change the system date from the control
panel of a UPS module.

Figure 30 Date screen

To reset the date, do the following at the SCC.
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor
to DATE.
2. Press the Select pad. The Date screen will appear.
3. Press the Select pad to move the arrow to the next digit to the right.
4. When the arrow is on the digit to be changed, press the Up pad to increase the number or the
Down pad to decrease it.
5. Press Select to set the value and move to the next digit.
6. After the correct month/day/year has been set, press the Select pad again to return to the System
Configuration screen.
NOTE
Precise Date and Time functions are required for accurate archival and event history purposes.
Both the Date and Time can be set from a remote terminal. Refer to 3.2.15 - Communication
Interfaces.
UP :
INCREASE VALUE
DOWN :
DECREASE VALUE
SELECT :
WALK-THRU/ EXIT