12.2.2 A-class Pump Specification
Power for drive
DC280-373V
Power for control
DC15±10%
Feedback Speed
(puls signal)
4puls/rotation
Control signal is analog voltage (DC0V-6V) generated by microcomputer PWM port.
Microcomputer can change analog voltage by changing PWM duty.
12.2.3 Water Flow Rate Setting
Set water pump speed to adjust the water flow rate.
Depend on the hyraulic system pressure loss and type, the water flow rate can be adjusted by control panel.
1
Press SERVICE button for 5 seconds.
2
Press
button to enter menu S02 and press SET button.
3
Press SELECt button then press
4
Press OFF/ON button to quit setting.
Note:
* Before adjust the water flow rate, make sure that the total water volume in the installation is minimum 50 litres for
heating side.
* Please ensure the minimum flow rate is not less than 13l/min and not more than 50l/min.
+
-
+
-
Control Signal
DC0V-DC6V
/
button to change SPEED and press SET to confirm.