16.5.21 Input Over Current Detection (F16)
Malfunction Decision Conditions:
During operation of heating, when outdoor current above 28.7A is detected by the current transformer (CT) in the
outdoor unit PCB.
Malfunction Caused:
1
Excessive refrigerant.
2
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 20 minutes.
107