16.5.26 Four Way Valve Abnormality (F25)
Malfunction Decision Conditions:
During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C.
Malfunction Caused:
1
Faulty sensor.
2
Faulty connector connection.
3
Faulty outdoor unit PCB (noise filter/main).
4
Faulty four way valve.
Abnormality Judgment:
Continue 4 times in 30 minutes.