19.17 DC Peak Current Detection (F32-09)

Malfunction Decision Conditions
During operation of cooling and heating, when DC peak is detected by the inverter DC Peak sensing circuitry in
the outdoor unit PCB (main).
Malfunction Caused
Faulty outdoor unit PCB (main).
Faulty compressor.
Abnormality Judgment
Continue for 7 times within 30 minutes (DC peak occur within 30 seconds compressor startup).
Continue for 3 times within 30 minutes (DC peak occur after 30 seconds compressor startup).
Troubleshooting
258