• Before remove the electrical control box cover, remove the cover plate and air filter.
• Remove the cover of the electrical control box by taking off the mounting screws (2 positions) and pushing the
hooking section. (The cover of the electrical control box remains hanged to the hinge.)
• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical control box.
(Do not apply tension to the connecting section of the terminal block.)
• Set a loop for the system interconnection wire of the storing part of the indoor unit electric parts; otherwise the
electrical control box cannot be drawn out in service time.
• Mount the cover of the electrical control box without pinching wires.
R(L)
S(N)
Power supply cord
Remote controller wire
Cable cramp
R
S
(L)
(N)
Earth wire
Power supply wire
 Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
▼ Wiring diagram
Terminal block for remote
controller wiring of indoor unit
A
B
 Address setup
Set up the addresses as per the Installation Manual supplied with the outdoor unit.
77-EN
Control wire
A
B
Electrical
control box
Electrical
control box
cover
Screw
(2 positions)
Remote controller wire
Terminal block
(Locally procured)
A
Remote controller unit
B
– 39 –
9

Applicable controls

REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatic address
setup
It takes up to 10 minutes (usually about 3 minutes) for
the outdoor unit to start operating after the power has
been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a wireless
remote controller, simple remote controller or group
control remote controller by itself so install a wired
remote controller separately as well.
Cover plate
 Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table: Do
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT31E). (There are more CODE No.)
1
3
4
6
5
2
1
1
Push and hold
button and "TEMP."
button simultaneously for at least 4
seconds. After a while, the display flashes
as shown in the figure. Confirm that the
CODE No. is [01].
If the CODE No. is not [01], push
button to clear
the display content, and repeat the procedure from
the beginning. (No operation of the remote
controller is accepted for a while after
button is
pushed.)
(While air conditioners are operated under the
group control, "ALL" is displayed first. When
is pushed, the indoor unit number
displayed following "ALL" is the header unit.)
(* Display content varies with the indoor unit
model.)
78-EN