C10/C20 Manual
6. FAULT FINDING
PROBLEM
POSSIBLE FAULT
Product frozen in
Ice bank too large
coil
Product warm
Reduced ice
weight or long
time to form ice
Product too warm
into cooler
Poor agitation of water
onto coils
Poor system installation
Note: Refrigeration system failure could be - Start device for compressor failed, over temperature device in compressor
tripped, open circuit on compressor motor windings, refrigerant gas leak, capillary tube blockage etc. These
faults are best diagnosed and repaired off site in a workshop environment.
POSSIBLE CAUSE
Faulty thermostat
Poorly positioned thermostat phial
Faulty thermostat
Fuse blown
No electrical supply
Refrigeration system failure
Poor condenser cooling
Insufficient water in tank
Keg badly positioned
Motor failure
Pump impeller failed
Excessive algae growth in bath
Poor airflow to condenser
5
®
ACTION
Replace
Reposition
Replace
Check and replace
Check
Replace unit
Check clearance
around cooler and
fan motor operation
Check clearance
around cooler and
fan motor operation.
Check condenser and
and clean if necessary
Top up water level
Reposition keg
Replace motor
Replace
Clean bath and coil
outer surface
Re-site cooler