SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
Indoor unit
[Model names]
[Service Ref.]
PLFY-P32VBM-E
PLFY-P32VBM-E.UK
PLFY-P32VBM-ER2.UK
PLFY-P40VBM-E
PLFY-P40VBM-E.UK
PLFY-P40VBM-ER2.UK
PLFY-P50VBM-E
PLFY-P50VBM-E.UK
PLFY-P50VBM-ER2.UK
PLFY-P63VBM-E
PLFY-P63VBM-E.UK
PLFY-P63VBM-ER2.UK
PLFY-P80VBM-E
PLFY-P80VBM-E.UK
PLFY-P80VBM-ER2.UK
PLFY-P100VBM-E
PLFY-P100VBM-E.UK
PLFY-P100VBM-ER3.UK
PLFY-P125VBM-E
PLFY-P125VBM-E.UK
PLFY-P125VBM-ER3.UK
Model name
indication
INDOOR UNIT
PLFY-P32VBM-E
.UK
1
PLFY-P32VBM-ER3.UK
PLFY-P40VBM-E
.UK
1
PLFY-P40VBM-ER3.UK
PLFY-P50VBM-E
.UK
1
PLFY-P50VBM-ER3.UK
PLFY-P63VBM-E
.UK
1
PLFY-P63VBM-ER3.UK
PLFY-P80VBM-E
.UK
1
PLFY-P80VBM-ER3.UK
PLFY-P100VBM-ER2.UK
PLFY-P125VBM-ER2.UK
CONTENTS
1. TECHNICAL CHANGES ......................... 2
2. SAFETY PRECAUTION .......................... 3
3. PART NAMES AND FUNCTIONS .......... 5
4. SPECIFICATIONS ................................. 13
5. 4-WAY AIR FLOW SYSTEM ................. 18
6. OUTLINES AND DIMENSIONS ............ 21
7. WIRING DIAGRAM ............................... 22
8. REFRIGERANT SYSTEM DIAGRAM ...... 24
9. TROUBLESHOOTING .......................... 25
10 . SPECIAL FUNCTION ........................... 34
11. DISASSEMBLY PROCEDURE ............. 41
PARTS CATALOG (OCB413)
December 2012
No. OCH413
REVISED EDITION-D
Revision:
PLFY-P32/40/50/63/80/
100/125VBM-ER3 have
been added in REVISED
EDITION-D.
• Some descriptions have
been modified.
• Please void OCH413
REVISED EDITION-C.
Note:
• This manual does not cover
outdoor units.
When servicing them, please
refer to the outdoor unit's
service manual.
• RoHS compliant products
have <G> mark on the spec
name plate.

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PLFY-P32VBM-E

  • Page 1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS December 2012 No. OCH413 REVISED EDITION-D TECHNICAL & SERVICE MANUAL Indoor unit [Model names] [Service Ref.] Revision: PLFY-P32VBM-E PLFY-P32VBM-E.UK PLFY-P32VBM-E PLFY-P32/40/50/63/80/ • PLFY-P32VBM-ER2.UK PLFY-P32VBM-ER3.UK 100/125VBM-ER3 have been added in REVISED PLFY-P40VBM-E PLFY-P40VBM-E.UK PLFY-P40VBM-E EDITION-D. PLFY-P40VBM-ER2.UK PLFY-P40VBM-ER3.UK...
  • Page 2: Technical Changes

    PLFY-P125VBM-ER2.UK PLFY-P125VBM-ER3.UK INDOOR CONTROLLER BOARD (I.B) has been changed. (S/W version up) PLP-6BAJ (Automatic filter elevation panel, option) The controller board (U.B) has been changed. (only for the panel but not for the service part) PLFY-P32VBM-E PLFY-P32VBM-ER2.UK PLFY-P40VBM-E PLFY-P40VBM-ER2.UK PLFY-P50VBM-E PLFY-P50VBM-ER2.UK...
  • Page 3: Safety Precaution

    SAFETY PRECAUTION Cautions for units utilizing refrigerant R410A Use the following tools specifically designed for Do not use the existing refrigerant piping. use with R410A refrigerant. The old refrigerant and lubricant in the existing piping The following tools are necessary to use R410A refrigerant. contains a large amount of chlorine which may cause the Tools for R410A lubricant deterioration of the new unit.
  • Page 4: Cautions For Service

    [1] Cautions for service (1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
  • Page 5: Part Names And Functions

    PART NAMES AND FUNCTIONS 3-1. INDOOR UNIT Drain pipe Filter Air outlet Liquid pipe Gas pipe i-see sensor (option) Vane Air intake (Intake grille) OCH413D...
  • Page 6: Wireless Remote Controller

    3-2. WIRELESS REMOTE CONTROLLER CHECK TEST RUN display CHECK and TEST RUN display indicate that the unit is being checked or test-run. MODEL SELECT display Blinks when model is selected. display Lights up while the signal is transmitted to the indoor unit when the button is pressed. display SET TEMP.
  • Page 7: Wired Remote Controller

    3-3. WIRED REMOTE CONTROLLER <PAR-30MAA/PAR-31MAA> Wired remote controller function * The functions which can be used are restricted according to the model. : Supported : Unsupported PAR-30MAA/PAR-31MAA Function PAR-21MAA Slim City multi Body Product size H × W × D (mm) 120 ×...
  • Page 8 The main display can be displayed in two different modes: "Full" and "Basic". The factory setting is "Full". To switch to the "Basic" mode, change the setting on the Main display setting. <Full mode> <Basic mode> * All icons are displayed for explanation. Cool Set temp.
  • Page 9 Menu structure Press the button. MENU Main menu Move the cursor to the desired item with the buttons, and press the SELECT button. Vane · Louver · Vent. (Lossnay) High power Timer On / Off timer Auto-Off timer Filter information Error information Weekly timer Energy saving...
  • Page 10 Main menu list Setting and display items Setting details Vane · Louver · Vent. Use to set the vane angle. (Lossnay) • Select a desired vane setting from fi ve different settings. Use to turn ON / OFF the louver. •...
  • Page 11 Setting and display items Setting details Initial setting Display Make the settings for the remote controller related items as necessary. details Clock: The factory settings are "Yes" and "24h" format. Temperature: Set either Celsius (°C) or Fahrenheit (°F). Room temp. : Set Show or Hide. Auto mode: Set the Auto mode display or Only Auto display.
  • Page 12: Display Section

    3-4. WIRED REMOTE CONTROLLER <PAR-21MAA> “Sensor” indication Display Section Displayed when the remote controller sensor is used. Day-of-Week For purposes of this explanation, Shows the current day of the week. all parts of the display are shown. During actual operation, only Time/Timer Display the relevant items will be lit.
  • Page 13: Specifications

    SPECIFICATIONS 4-1. SPECIFICATIONS Model PLFY-P40VBM-E PLFY-P50VBM-E PLFY-P32VBM-E PLFY-P63VBM-E Power source 1-phase 220-240V 50Hz, 1-phase 220V 60Hz Cooling capacity kcal / h 3,900 4,800 (Nominal) 3,100 6,100 Btu / h 12,300 15,400 19,100 24,200 kcal / h 3,150 4,000 5,000 6,300 Power input 0.03...
  • Page 14 Model PLFY-P80VBM-E PLFY-P100VBM-E PLFY-P125VBM-E 1-phase 220-240V 50Hz, 1-phase 220V 60Hz Power source 11.2 14.0 Cooling capacity kcal / h 7,700 9,600 12,000 (Nominal) Btu / h 30,700 38,200 47,800 kcal / h 8,000 10,000 12,500 0.16 Power input 0.07 0.15 Current input 0.51 1.00...
  • Page 15: Electrical Parts Specifications

    4-2. ELECTRICAL PARTS SPECIFICATIONS PLFY-P32VBM-E.UK PLFY-P40VBM-E.UK PLFY-P50VBM-E.UK PLFY-P63VBM-E.UK Service Ref. PLFY-P32VBM-E PLFY-P40VBM-E PLFY-P50VBM-E PLFY-P63VBM-E Symbol PLFY-P32VBM-ER2.UK PLFY-P40VBM-ER2.UK PLFY-P50VBM-ER2.UK PLFY-P63VBM-ER2.UK PLFY-P32VBM-ER3.UK PLFY-P40VBM-ER3.UK PLFY-P50VBM-ER3.UK PLFY-P63VBM-ER3.UK Parts name Room temperature Resistance 0 /15k , 10 /9.6k , 20 /6.3k , 25 /5.4k , 30 /4.3k , 40 /3.0k...
  • Page 16: Sound Level

    (1, 2) Rated to 250V 10A * terminal block * Note: Refer to WIRING DIAGRAM for the supplied voltage. 4-3. SOUND LEVEL Sound level at anechoic room : Low- Mid2-Mid1 -High PLFY-P·VBM-E Service Ref. Sound level dB (A) PLFY-P32VBM-E 27-28-29-31 PLFY-P32VBM-ER2.UK PLFY-P32VBM-ER3.UK PLFY-P40VBM-E PLFY-P40VBM-ER2.UK PLFY-P40VBM-ER3.UK 27-28-30-31 PLFY-P50VBM-E PLFY-P50VBM-ER2.UK...
  • Page 17 4-4. NC CURVES PLFY-P32VBM-E PLFY-P40VBM-E PLFY-P50VBM-E PLFY-P32VBM-ER2.UK PLFY-P40VBM-ER2.UK PLFY-P50VBM-ER2.UK PLFY-P32VBM-ER3.UK PLFY-P40VBM-ER3.UK PLFY-P50VBM-ER3.UK External static pressure : 0Pa External static pressure : 0Pa External static pressure : 0Pa Power source : 220,230,240V, 50Hz / 220V, 60Hz Power source : 220,230,240V, 50Hz / 220V, 60Hz...
  • Page 18: Way Air Flow System

    4-WAY AIR FLOW SYSTEM 5-1. PLACEMENT OF THE AIR OUTLETS • For this grille, the blowout direction comes in 11 patterns. Also, by setting the remote controller to the appropriate settings, you can adjust the airflow and speed. Select the settings from Table1 according to the location in which you want to install the unit.
  • Page 19 5-2. BRANCH DUCT HOLE AND FRESH AIR INTAKE HOLE At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. Note: The figures marked with * in the drawing below represent the dimensions of the main unit excluding those of the optional multi function casement.
  • Page 20 5-4. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS PLFY-P32/40/50/63/80VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80VBM-ER2.UK PLFY-P32/40/50/63/80VBM-ER3.UK Multi function casement + Standard filter Multi function casement + High efficiency filter 2 - inlet 2 - inlet -100 -100 -150 -150 1 - inlet 1 - inlet -200 -200 Airflow rate [m...
  • Page 21: Outlines And Dimensions

    OUTLINES AND DIMENSIONS PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80/100/125VBM-ER2.UK Unit : mm PLFY-P32/40/50/63/80/100/125VBM-ER3.UK Ceiling hole 20~45 860~910 20~45 Detail connecting of branch duct(Both aspects) Fresh air Suspension bolt pitch Cut out hole intake hole Indoor/outdoor unit connecting terminal block Power supply Branch duct hole 14- 2.8 terminal block Branch duct hole...
  • Page 22: Wiring Diagram

    WIRING DIAGRAM PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80/100/125VBM-ER2.UK [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME I. B INDOOR CONTROLLER BOARD TERMINAL POWER SUPPLY OPTION PART CN27 CONNECTOR DAMPER BLOCK TRANSMISSION PCB FOR WIRELESS REMOTE CONTROLLER REMOTE SWITCH MA-REMOTE CONTROLLER CN32 TB15 BUZZER CENTRALLY CONTROL ROOM TEMP.
  • Page 23 PLFY-P32/40/50/63/80/100/125VBM-ER3.UK LEGEND SYMBOL NAME SYMBOL NAME SYMBOL NAME I. B INDOOR CONTROLLER BOARD DRAIN-UP MACHINE A. B ADDRESS BOARD CN27 DRAIN FLOAT SWITCH SWITCH CEILING HEIGHT SELECTOR CONNECTOR DAMPER CN32 REMOTE SWITCH LINEAR EXPANSION VALVE DISCHARGE OUTLET NUMBER CN51 CENTRALLY CONTROL FAN MOTOR SELECTOR CN52...
  • Page 24: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80/100/125VBM-ER2.UK PLFY-P32/40/50/63/80/100/125VBM-ER3.UK Strainer (#100mesh) Gas pipe thermistor TH23 Gas pipe Liquid pipe thermistor TH22 Flare connection Liquid pipe Heat exchanger Linear expansion valve Strainer1 (#50mesh) Strainer2 (#100mesh) Strainer (#100mesh) Room temparature thermistor TH21 Unit : mm(inch) Capacity PLFY-P32/40VBM-E PLFY-P50VBM-E...
  • Page 25: Troubleshooting

    TROUBLESHOOTING 9-1. HOW TO CHECK THE PARTS PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80/100/125VBM-ER2.UK PLFY-P32/40/50/63/80/100/125VBM-ER3.UK Parts name Check points Room temperature Disconnect the connector then measure the resistance with a tester. thermistor (TH21) (At the ambient temperature of 10 - 30 ) Liquid pipe thermistor (TH22) Normal Abnormal...
  • Page 26: Linear Expansion Valve

    9-1-1. Thermistor < Thermistor for lower temperature > <Thermistor characteristic graph> Thermistor for Room temperature thermistor (TH21) lower temperature Liquid pipe temperature thermistor (TH22) Gas pipe temperature thermistor (TH23) Thermistor R =15k' ± 3% Fixed number of B=3480 ± 2% Rt=15exp { 3480( 273+t 15k'...
  • Page 27 <Output pulse signal and the valve operation> Output Output Closing a valve : 1 → 2 → 3 → 4 → 1 (Phase) Opening a valve : 4 → 3 → 2 → 1 → 4 The output pulse shifts in above order. •...
  • Page 28 9-1-3. DC Fan motor (fan motor/indoor controller board) Check method of indoor fan motor (fan motor/indoor controller board) Notes · High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service. · Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller board and fan motor) Self check Conditions : The indoor fan cannot turn around.
  • Page 29: Function Of Dip Switch

    9-2. FUNCTION OF DIP SWITCH The black square (■) indicates a switch position. Operation by switch Effective Switch Pole Function Remarks timing Thermistor <Room temperature Address board Built-in remote controller Indoor unit detection> position <Initial setting> Filter clogging detection Provided Not provided Filter cleaning 2,500hr...
  • Page 30 Effective Switch Pole Operation by switch Remarks timing Address board Ceiling height can be changed depends on SWB setting. (High ceiling) <Initial setting> Ceiling (Standard) height PLFY-P32·P40·P50·P63·P80VBM-E (Silent) selector Silent Standard High ceiling 4 direction 2.5m 2.7m 3.5m 3 direction 2.7m 3.0m 3.5m...
  • Page 31 Effective Switch Pole Operation by switch Remarks timing <Initial setting> • To operate each indoor unit by each remote controller when installed 2 indoor units or more are near, Pair No. setting is necessary. Pattern A Pair No. setting is available with the 4 patterns (Setting patters A to D). Make setting for J41, J42 of indoor controller board and the Pair No.
  • Page 32: Test Point Diagram

    9-3. TEST POINT DIAGRAM 9-3-1. Indoor controller board PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80/100/125VBM-ER2.UK PLFY-P32/40/50/63/80/100/125VBM-ER3.UK CN6Y CN60 i-See sensor motor output Linear expansion valve (LEV) 12VDC pulse output output 12VDC pulse output CN3A CN4Y Connect to the terminal block (TB15) i-See sensor (MA-Remote controller connecting wire) 1 - 3 : 8.7-13V DC (Pin1 (+)) CN52 Remote indicator...
  • Page 33 9-3-2. Address board PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80/100/125VBM-ER2.UK PLFY-P32/40/50/63/80/100/125VBM-ER3.UK Ceiling height Discharge outlet Function setting number selector selector SW12 SW11 SW14 Address setting Address setting Branch No. Option selector 10ths digit 1s digit OCH413D...
  • Page 34: Special Function

    SPECIAL FUNCTION 10-1. HOW TO PERFORM THE UP/DOWN OPERATION OF THE AIR INTAKE GRILLE 10-1-1. Setting up the lowering distance of air intake grille Unit You can set up 8 different stages of lowering distance for Decorative the air intake grille according to the set up location if desired. panel * As a factory default, the decorative panel will automatically stop at 1.6 m from the ceiling surface.
  • Page 35 10-1-3. How to perform the up/down operation using wired remote controller (PAR-30MAA / PAR-31MAA) Maintenance menu Select "Maintenance" from the Main menu, and press the button. Auto descending panel Manual vane angle Select "Auto descending panel" with the F1 or F2 button, and press the button.
  • Page 36 10-1-4. How to perform the up/down operation using wired remote controller (PAR-21MAA) General Operation * Raise or lower all the air intake grilles managed by the remote controller at the same time. Install the remote controller in a place where you can observe all the air-conditioners. Otherwise, the lowering grille may make contact with something and cause damage to it.
  • Page 37 ■ Up/down operation with the individual specified air-conditioner (when used in combination with Mr. SLIM model) * Raise or lower the air intake grille of the specific air-conditioner that you select from all that are managed by that remote controller. 1) Ensure that the air-conditioner is not running.
  • Page 38: Normal Operation

    10-2. OPERATION (AUTO DESCENDING PANEL: PLP-6BAJ) (1) Normal operation UP/DOWN Wire 1b Air intake grille is raised/lowered by UP/DOWN UP/DOWN commands of UP and DOWN. Machine 2 Machine 1 Air intake grille does not move under the state of no-load detection or obstacle detection. Air intake grille stops automatically at the set lowering distance from the ceiling level.
  • Page 39 10-3. ELECTRICAL CIRCUIT (Controller board and wiring diagram (Panel)) 10-3-1. Dip SW 22 type SW22 Panel Indoor unit (WHT) LS21 CN3G CN90 (WHT) (BLK) CN2G (BLK) CN3G (BLK) FUSE CN22 (BLU) CN2F (BLK) CNAC (WHT) CN2E LS21 (RED) CN2B CN2C (WHT) GRN/YLW (WHT)
  • Page 40: Troubleshooting

    10-3-3. Check point of trouble <LED (SW22 type) /LED2 (SW2 type) display> Turn OFF : No power supply Blink : Storage detection switch ON (short) One blink : Storage detection switch OFF (open) Two blinks : Tension detection switch OFF (open) <controller board>...
  • Page 41: Disassembly Procedure

    DISASSEMBLY PROCEDURE PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E PLFY-P32/40/50/63/80/100/125VBM-ER2.UK PLFY-P32/40/50/63/80/100/125VBM-ER3.UK Be careful when removing heavy parts. OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 1. Removing the air intake grille Figure 1 Filter (1) Slide the knob of air intake grille toward the arrow 1 to open the air intake grille. (2) Remove drop prevention hook from the panel.
  • Page 42 OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS Coil plate Photo 3 6. Removing the fan and fan motor (MF) (1) Remove the electrical box. (See Photo 2) (2) Remove the bell mouth (3 screws). (See Photo 2) (3) Remove the turbo fan nut. (4) Pull out the turbo fan.
  • Page 43 OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS Photo 8 10 Removing the drain pump (DP) and float switch (FS) (1) Remove the drain pan. (See Photo 6) (2) Cut the hose band and remove the hose. (3) Remove the drain pump assembly (3 screws and 2 hooks). Float switch (4) Remove the drain pump (3 screws).
  • Page 44 HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN cCopyright 2007 MITSUBISHI ELECTRIC CORPORATION Distributed in Dec. 2012 No. OCH413 REVISED EDITION-D Distributed in Aug. 2009 No. OCH413 REVISED EDITION-C PDF 6 Distributed in Feb. 2009 No. OCH413 REVISED EDITION-B PDF 6 New publication, effective Dec.