On roof terminations, the intake piping should termi-
nate straight down using two 90 ° elbows. See figure 8.
NOTE - If winter design temperature
is below 32°F (O°C),
exhaust piping must be insulated
with 1/2 inch (13 mm)
Armaflex
or equivalent
when
run
through
unheated
space.
Do not leave any surface
area of exhaust pipe
open to outside air," exterior exhaust
pipe must be insu-
lated with 1/2 inch (13 ram) Armaflex or equivalent. In ex-
treme cold climate areas, 3/4 inch (19 mm) Armaflex
or
equivalent
is recommended.
Insulation on outside runs of
exhaust pipe must be painted
or wrapped to protect in-
sulation from deterioration.
NOTE
- During
extremely
cold
temperatures,
below
approximately
20°F (6.67°C), units with long runs of vent
pipe through unconditioned
space, even when insulated,
may form ice in the exhaust termination
that prevents the
unit from operating properly. Longer run times of at least 5
minutes will alleviate most icing problems. Also, a heating
cable may be installed on exhaust piping and termination
to prevent
freeze-ups.
Heating
cable installation
kit is
available
from Lennox.
See Condensate
Piping section
for part numbers.
NOTE - Care must be taken to avoid recirculation
of ex-
haust back into intake pipe.
6 - On field-supplied
terminations
for side wall exits, ex-
haust piping should extend a maximum of 12 inches
(305 mm) beyond
the outside
wall. Intake piping
should be as short as possible.
See figure 10.
IMAX.
Inches
(ram)
3 x 2 (70 x 51) OR
2 x %1/2 (51 x 38)
PVC REDUCER
1/2 (13) FOAM
INSULATION
IN
UNCONDrrlONED
12 (305) ABOVE
SPACE
AVERAGE SNOW
ACCUMULATION
3 (76) OR
UNCONDmONED
2 (5t) PVC
ATTIC SPACE
PROVIDE SUPPORT
FOR INTAKE AND
F.XHAUST LINES
ROOFTERMINATION KIT
(15F'75) L B-49107CCfor 2 (5t) Venting
(44341)LB-65678Afor 3 (76)Venting
FIGURE
8
EXHAUST
12 (305)
ABOVE
AVERAGE
SNOW
ACCUMULATION
INTAKE
TERMINATION
Inches (mm)
EXHAUST
INTAKE
CONCENTRIC ROOFTOP TERMINATION
(60G77) LB-49107CE for G32-75 Units Only
(33K97) LB-87942 for G32-100 & -125 Units Only
FIGURE 9
1/2 (13) ARMAFLEX
INSULATION IN
UNCONDITIONED
SPACE
1/2 (13) ARMAFLEX
t'
INSULATION
OUTSIDE
j
WALL
12 (305) MIN.
2 X 1-1/2
(51 X 38)
PV
REDUCER
_ _
'VC
I
6 (I 52)
MAXIMUM
_
2 (_ I PVC
PLING
Inches (ram)
7-
8-
TOPVIEW
WALL RINGKIT
(15J74)
LB-49107CB f or
2 (50,8 ! Venting
FIGURE 10
On field-supplied terminations, a minimum separa-
tion distance between the end of the exhaust pipe
and the end of the intake pipe is 8 inches (203 mm).
If intake and exhaust piping must be run up a side
wall to position above snow accumulation or other
obstructions, the piping must be supported every 3
feet (.91 m) as shown in figure 15. Refer to figures 13
and 14 for proper piping method. W'FK wall termina-
tion kit must be extended for use in this application,
See figure 18 or use kit WTKX shown in figure 19.
When exhaust and intake piping must be run up an
outside wall, the exhaust piping is reduced to 1-1/2
inches (38 mm) after the final elbow. The intake pip-
ing may be equipped with a 90 ° elbow turndown. Us-
ing 90 ° turndown will add 5 feet (1.5 m) to the equiva-
lent length of the pipe.