2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote
controller.
(A) ON the set temperature display part, "CHECK" appears, and
the unit address and the check code are displayed alternately
at one-second intervals. (Check mode)
Example
Alternately
displayed
CHECK
0
°F
(2) When one remote controller controls several units in the group control,
the LCD shows the unit address and check code of the first malfunc-
tioning unit.
(3) To cancel the check mode, press the POWER
remote ON/OFF control, press the remote ON/OFF switch. In central-
ized control, turn OFF the POWER ON/OFF button of centralized con-
troller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
2-2 How to use the self diagnostic function for service
A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) During the self diagnostic function, "CHECK" appears at two positions on the remote controller display. Then, at least
10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
2-3 For group control using one remote controller
(1) Press the WARMER or COOLER button on the remote controller to advance or go back to the unit address. Each time
WARMER button is pressed, the unit address advances by one. Each time COOLER button is pressed, the unit
address goes back by one.
The check code and the unit address, appear alternately.
(2) The check code "U8" means no malfunction has occurred since installation.
The check code "EO" means the following conditions:
The unit address displayed on the remote controller does not apply to any unit.
power is not supplied to the unit.
Signal transmitting / receiving circuit is abnormal.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
52
CHECK
p1
°F
ON/OFF
CHECK mode
button. In
-CENTRALLY CONTROLLED-
POWER
ON/OFF
STAND BY
ON
DEFROST
CHECK DRY
HEAT
AUTO
COOL/DRY
HEAT
COOL
CHECK
SET
WARMER
COOLER
SET TEMP
F
TEMPERATURE
TIMER OFF
TIMER
MODE
HOURS
AUTO STOP
HR
AUTO START
LOW HIGH
FAN SPEED LOW/HIOGH
AIR
SWING
UP/DOWN
STOP
DISCHARGE
F
AUTO RETURN
CHECK TEST RUN
CHECK
TEST RUN
MITSUBISHI ELECTRIC
CHECK button

Hide quick links: