Water Vapor: A By-Product Of Unvented Room Heaters; Provisions For Adequate Combustion And Ventilation Air - Empire Heating Systems SR-10T-3 Installation Instructions And Owner's Manual

Unvented room heater
Table of Contents

Advertisement

Available languages

Available languages

WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS

Water vapor is a by-product of gas combustion. An unvented room
heater produces approximately one (1) ounce (30ml) of water for
every 1,000 BTU's (.3KW's) of gas input per hour.
Unvented room heaters must be used as supplemental heat (a
room) rather than a primary heat source (an entire house). In most
supplemental heat applications, the water vapor does not create a
problem. In most applications, the water vapor enhances the low
humidity atmosphere experienced during cold weather.
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR
This heater shall not be installed in a confined space or unusually
tight construction unless provisions are provided for adequate
combustion and ventilation air.
A confined space is an area with volume less than 50 cubic feet per
1,000 Btuh of the combined input rates of all appliances drawing
combustion air from that space. Small areas such as equipment
rooms are confined spaces. Furnaces installed in a confined space
which supply heated air to areas outside the space must draw return
air from outside the space through tightly sealed return air ducts. A
confined space must have 2 openings into the space for combus-
tion air. One opening must be within 12 inches of the ceiling and
the other must be within 12 inches of the floor. The required sizing
of these openings is determined by whether inside or outside air is
used to support combustion, the method by which the air is brought
to the space (vertical or horizontal duct) and by the total input rate
of all appliances in the space.
The following example is for determining the volume of a typical
area in which the SR-30T may be located and for determining if this
area fits the definition of an unconfined space.
The input of the SR-30T is 30,000 Btu per hour. Based on the 50
cubic feet per 1,000 Btu per hour formula, the minimum area that
is an unconfined space for installation of the SR-30T is 1,500 cubic
feet, 50 cubic feet x 30 = 1,500 cubic feet. To determine the cubic
feet of the area in which the SR-30T is to be installed, measure the
length, width and height of the area. Example: The area measures
16 feet in length, 12 feet in width and 8 feet in height, the area is
1,536 cubic feet. The SR-30T can be installed in this unconfined
space with no requirement to provide additional combustion and
ventilation air.
If the area in which the heater may be operated is smaller than that
defined as an unconfined space or if the building is of unusually
tight construction, provide adequate combustion and ventilation
air by one of the methods described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation,
or applicable local codes.
Page 6
WARNING
The following steps will help insure that water vapor does not
become a problem.
1. Be sure the heater is sized properly for the application, including
ample combustion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used to
help lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat source
(an entire house).
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction
where:
a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm
or less with openings gasketed or sealed, and
b. Weatherstripping has been added on openable windows and
doors, and
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical, and gas lines, and at
other openings.
If the SR-30T heater is installed in a building of unusually tight
construction, adequate air for combustion, ventilation and dilution
of flue gases shall be provided in accordance with ANSI Z223.1/
NFPA54.
16941-8-0314

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Sr-18t-3Sr-30t-3

Table of Contents