Function
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor unit
35°C
Heat-Exchanger
temperature
32°C
29°C
21°C
17°C
Intake Air Temperature
Setting Temperature
+3°C
(Thermo OFF)
Setting Temperature
(Thermo ON)
COMP
Outdoor fan
Indoor fan
4way valve
• Compressor-off interval : -
136 Synchro Air Conditioner
1min
ON
ON
Setting
Lo
fan
Off
Low
Low
spped
A
While the indoor Heat-Exchanger temperature is higher than 35°C, fan operates
at low speed, when it becomes lower than 35°C fan stops.
B
-
For eluminating latent heat-loss, fan operates at low speed for 10 seconds
periodically.
3min
Minimum
3min
OFF
OFF
Setting
fan
Low
Low
Off
spped
ON
A
Low fan during 10sec
B
1min
ON
ON
Setting
fan
Off
Low
spped