SEE-THROUGH INSTALLATION PROCEDURE
VENTING
Refer to pages 6-13. All venting must have a minimum clear-
ance of 2" to combustible material on the top and 1" to the
sides and bottom.

FRAMING

See Page 18 for additional framing dimensions.
Note: In order to avoid the possibility of exposed insula-
tion or vapour barrier coming in contact with the
fi replace body, it is recommended that the walls of the
fi replace enclosure be "fi nished" (ie: drywall/sheetrock), as
you would fi nish any other outside wall of a home. This will
ensure that clearance to combustibles is maintained within
the cavity.
It is best to frame your fi replace after it is positioned and the
vent system is installed. Use 2x4's and frame to local build-
ing codes.
See PAGE 14 for bar type / countertop installation.
FIGURE 23
A = 22" minus fi nishing material thickness, each side.
BRICK PANEL INSTALLATION
Install the base panels as illustrated in steps 1-4 on page 15.
Both side panels sit under the bracket tab
panel in position, bend down the tab to secure. DETAIL 6.
DETAIL 5 & 6
.
Holding the side
FIGURES 24a-c
RETAINER
STEP 5
RETAINER
STEP 6
FACING
Combustible materials may be installed fl ush with the front of
the fi replace but must not cover any of the black face-areas
of the fi replace. Non-combustible material (brick, stone or
ceramic tile) may protrude in these areas.
It is not necessary to install a hearth extension with this fi re-
place system.
When roughing in the fi replace, raise the fi replace to accom-
modate for the thickness of the fi nished fl oor materials, i.e.
tile, carpeting, hard wood, which if not planned for will interfere
with the opening of the lower access door and the installation
of many decorative fl ashing accessories.
Objects placed in front of the fireplace should be
kept a minimum of 48" away from the glass front
faces.
FINISHING
Refer to pages 23-26 for complete instructions regarding
mantle requirements and installations, log placement, glass
door and upper and lower louvre attachments.
FIGURE 25
DRYWALL
17
DRYWALL
5" MIN
W415-0299 / H / 10.16.07