Series 3

Connect oil piping

General oil piping requirements:
Location and installation of oil tanks, oil piping and
burners must follow:
• NFPA 31, Standard for the Installation of Oil-Burning
Equipment.
• In Canada, CSA B139, Installation of Oil-Burning
Equipment.
• Local codes and regulations.
• Information provided with burner and
If any part of fuel oil tank is above level of burner,
an anti-siphon device must be used to prevent fl ow
of oil in case of oil line break.
Support oil lines as required by codes.
Make tank connections with swing joints or copper
tubing to prevent breaking in case the tank settles.
Figure 16 Recommended oil piping connection to burner (follow applicable code requirements and
22
— Boiler Manual
WATER BOILER
burner manual for component locations)
Make swing joints so they will tighten as tank settles.
Non-hardening pipe joint compounds should be
used on all threads.
Underground pipe must be run in a casing to pre-
vent oil leaking into ground or under fl oor. Check
fuel pump.
local codes for information.
Oil piping connection at burner:
See Figure 16 for recommended connection at
burner, allowing burner mounting door to swing
open completely for servicing.
Do not use Tefl on tape as an oil pipe seal-
ant. It can cause valves to fail, creating
hazards. Do not use compression fi ttings.
Part number 550-142-182/1014