Thermostat Wiring - Weil-McLain UltraOil Series 3 Installation, Start-Up, And Operating Instructions Manual

Oil-fired water boiler
Hide thumbs Also See for UltraOil Series 3:
Table of Contents

Advertisement

®
Series 3
Connect wiring
Remove the Control Pod cover to facilitate wire routing. (To
remove, push the Control Pod cover to one side, and gently
work the cover retainer hinge on the other side out of the
jacket slot.)
120-volt wiring
Conduits
Connect each conduit supplying line-voltage wiring to or
from the boiler to a conduit opening in the upper portion of
the jacket rear panel.
All fi eld-provided line-voltage wiring must be sheathed in
fl exible metal conduit.
Additional limits
If required by state or local codes, provide additional limits
as needed.
When using additional limits, remove the factory-installed
jumper between boiler terminal strip terminals 19 and 20.
Connect the additional limits in series and wire to boiler
terminal strip terminals 19 and 20.
Circulator
The circulator is shipped with the boiler, but not installed or
wired.
Wire the circulator to the boiler terminal strip as shown on
the boiler wiring diagram. Provide hot, neutral and ground
wires, routed in metal conduit.

Thermostat wiring

Install thermostat on inside wall away from infl uences of
drafts, hot or cold water pipes, lighting fi xtures, televisions,
sun rays or fi replaces.
Follow instructions with thermostat.
If the thermostat has a heat anticipator, set the heat anticipator
per the limit control manufacturer's recommendation.
Burner wiring (see Figure 14)
The burner harnesses incorporate disconnect plugs, providing
a convenient way to disconnect wiring when burner mounting
door is opened.
Failure to disconnect the burner wiring harness
before opening the burner door can cause damage
to the burner and boiler wiring.
Optional AFM installation
See separate AFM instructions when used.
When wiring is completed:
Reinstall the Control Pod cover, close cover and tighten the
retainer screw.
Replace jacket top and secure with screws.
Part number 550-142-182/1014
— Boiler Manual
WATER BOILER
Figure 14 Burner harness routing
19

Advertisement

Table of Contents
loading