3-2-2(h) Refrigerant Adjustment
Class
Connection
Air-Purge
Pipe Length
Method
5m Max.
Refer to the
detailed Air-Purge
Procedure
5~10m
3-2-2(i) Flare nut fixing torque
Outer diameter
ø 6.35 (Liquid Side)
ø 9.52 (Gas Side)
ø 12.7 (Gas Side)
Samsung Electronics
For installation
Refrigerant
Adjustment
Unnecessary
Add 20g of refrigerant
R410A(Add as liquid
state) for every 1m.
Fixing Torque
Air-Purge
Method
Purge air using a
vaccum pump
Torque (kg-cm)
160
300
500
Operating Instructions and Installation
For service
Refrigerant
Quantity
refer to
specification sheet
Add 20g of refrigerant
R410A(Add as liquid
state) for every 1m.
Final Torque
200
350
550