Power Supply - Mitsubishi Electric FR-A8AP Instruction Manual

Hide thumbs Also See for FR-A8AP:
Table of Contents

Advertisement

 Power supply
Choose a power supply for encoder according to the encoder used (5 V/12 V/15 V/24 V). When the encoder output is the
differential line driver type, only 5 V can be input. Make sure the voltage of the external power supply the same as the encoder
output voltage. (Check the encoder specification.)
When an encoder is used under orientation control, encoder feedback control, and vector control, the power supply is shared
between the inverter and encoder.
• Specifications of the encoders equipped in the motors with encoders and the vector-control dedicated motors
Item
Resolution
1024 pulses/rev
Power supply voltage
5 VDC±10%
Current consumption
150 mA
A, B phases (90° phase shift)
Output signal form
Z phase: 1 pulse/rev
Output circuit
Differential line driver 74LS113 equivalent
H level: 2.4 V or more
Output voltage
L level: 0.5 V or less
NOTE
• When the input power supply voltage to the encoder and its output voltage differ, the protective function (E.ECT) may
be activated.
20
ENCODER SPECIFICATIONS AND PARAMETER SETTINGS
Encoder for SF-JR/HR/JRCA/HRCA
Encoder for SF-V5RU, SF-THY
2048 pulses/rev
12 VDC±10%
Complementary
H level: "Power supply for encoder-3 V" or more
L level: 3 V or less

Advertisement