Main Circuit Terminal Specifications; Specification Of Main Circuit Terminal; Terminal Arrangement Of The Main Circuit Terminal, Power Supply And The Motor Wiring - Mitsubishi Electric FR-E720-600 Instruction Manual

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

2.2

Main circuit terminal specifications

2.2.1

Specification of main circuit terminal

Terminal
Terminal Name
Symbol
R/L1,
S/L2,
AC power input
T/L3
U, V, W
Inverter output
P/+, PR
Brake resistor connection
P/+, N/-
Brake unit connection
P/+, P1
DC reactor connection
Earth (Ground)
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
200V class
FR-E720-008 to 050
Screw size (M3.5)
N/-
R/L1 S/L2 T/L3
Screw size
(M3.5)
Power supply
FR-E720-240, 330
Screw size (M5)
R/L1 S/L2 T/L3
N/-
Screw size
Power supply
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter (FR-HC) or
power regeneration common converter (FR-CV).
Connect a three-phase squirrel-cage motor.
Connect a brake transistor (FR-ABR, MRS, MYS) across terminals P/+-PR.
(The brake resistor can not be connected to the FR-E720-008 or 015.)
Connect the brake unit (FR-BU2), power regeneration common converter (FR-CV)
or high power factor converter (FR-HC).
Remove the jumper across terminals P/+-P1 and connect a DC reactor.
For earthing (grounding) the inverter chassis. Must be earthed (grounded).
Jumper
P/+
PR
IM
Motor
P/+ PR
Jumper
(M5)
IM
Motor
Main circuit terminal specifications
Description
FR-E720-080 to 175
Jumper
N/- P/+
Screw size (M4)
R/L1 S/L2 T/L3
PR
Power supply
FR-E720-470, 600
Screw size(470:M5/600:M6)
R/L1 S/L2 T/L3
N/-
Screw size
Power supply
IM
Screw size
(M4)
Motor
P/+
PR
Jumper
IM
(M5)
Motor
2