Grounding The Switch By Using The Ac Power Cord - HP 5920 Switch Series Installation Manual

Hide thumbs Also See for 5920 Switch Series:
Table of Contents

Advertisement

NOTE:
HP recommends that you use the primary grounding point or auxiliary grounding point 1, because the
grounding cable and grounding screw provided with the switch are applicable only to these two
grounding points.
To use auxiliary grounding point 2 on the HP 5900AF-48XG-4QSFP+, 5900AF-48XG-4QSFP+ TAA,
5900CP-48XG-4QSFP+, 5900CP-48XG-4QSFP+8Gb FC B-F, 5900AF-48XGT-4QSFP+, and
5900AF-48G-4XG-2QSFP+ switches, you must prepare a grounding cable yourself. The connection
method is the same as connecting to the other two grounding points.

Grounding the switch by using the AC power cord

If the installation site has no grounding strips, you can ground an AC-powered switch through the
protective earth (PE) wire of the power cord, but must make sure:
The power cord has a PE terminal.
The ground contact in the power outlet is securely connected to the ground in the power distribution
room or on the AC transformer side.
The power cord is securely connected to the power outlet.
NOTE:
If the ground contact in the power outlet is not connected to the ground, report the problem and reconstruct
the grounding system.
Figure 14 Grounding through the PE wire of the AC power cord
(1) Three-wire AC power cable
1
(2) Chassis rear panel
14
2