Operating mode

Setpoints

Room temperature
Siemens Switzerland Ltd
HVAC Products
6.6

Heating circuits

For the heating circuits, various functions are available which can
B9
be individually set for each heating circuit.
Y1/Y2
Q2
B1
H
RG1
Line no.
1300
The operating mode of heating circuits 1 and 2 is selected directly with the operating
mode button while the operating mode of heating circuit P must be selected in
programming mode (1300).
This setting is used to switch between the different operating modes. The functionality
corresponds to operating mode selection with the operating mode button. For details,
refer to section "Operation".
Line no.
HC1
HC2
HC3P
710
1010 1310
712
1012 1312
714
1014 1314
716
1016 1316
The room temperature can be shifted according to different setpoints. These setpoints
become active depending on the selected operating mode, thus producing different
temperature levels in the rooms.
The setpoint setting ranges are obtained as a result of the interdependency of
setpoints. This is shown in the following graph:
0
2
4
6
TRKmax Comfort setpoint max
TRK
Comfort cooling setpoint
TRR
Reduced setpoint
TRF
Frost protection setpoint
User manual RVS61.843, RVS41.813
6 The settings in detail
The operating lines of the second heating circuit appear only
when an AVS75.390 extension module is connected to the
controller.
The operating lines of the pump heating circuit appear only
when a multifunctional output is defined as the pump heating
circuit.
Operating line
Operating mode
Protection
Automatically
Reduced
Comfort
Operating line
Comfort cooling setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint max
TRR
TRF
8
10
12
14
16
TRKmax
TRK
18
20
22
24
26
2358Z01
CE1U2355en_02
28. September 2009
°C
85/258