Buderus LOGANO PLUS GB312 Installation Instructions Manual page 61

Gas condensing boiler
Table of Contents

Advertisement

Display
1)
Type
code
Fault code
L
EE
601
L
EE
612
L
EE
626
Table 22 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 – 6 720 647 367 (2012/11)
Cause
Description
Flow temperature sensor
Successive flow
reading.
temperature readings
are too widely divergent.
Return sensor reading.
Successive return
temperature readings
are too widely divergent.
Electrode voltage incorrect. Voltage to ionization
electrode too low.
Troubleshooting
Testing sequence/
Cause
Measure
Check lead to boiler
Replace if damaged.
sensor.
Check connector.
If dirty, clean
or replace as necessary.
If connector is loose,
reconnect properly.
Check sensor readings
Replace temperature
against table.
sensor if there are
discrepancies.
Check temperature
Replace SAFe
sensor voltage levels
if there are
against table.
discrepancies.
Check lead to boiler
Replace if damaged.
sensor.
If dirty, clean
or replace as necessary.
Check connector.
If connector is loose,
reconnect properly.
Check sensor readings
Replace temperature
against table.
sensor if there are
discrepancies.
Check temperature
Replace SAFe
sensor voltage levels
if there are
against table.
discrepancies.
Check connecting lead
Replace defective lead
between SAFe and
or rectify breaks.
electrode for breaks or
damage.
Check electrode gaps and
Align burner rod/
electrode for damage.
electrode Replace
defective electrode.
Check power supply
Ensure power supply
voltage at MC10 input
voltage is correct.
(at least 102 V).
Check if voltage dips are
Eliminate voltage dips.
occurring (e.g. when large
electrical consumers are
switched on)
If all checks OK, replace
SAFe.