Buderus LOGANO PLUS GB312 Installation Instructions Manual page 55

Gas condensing boiler
Table of Contents

Advertisement

Display
1)
Type
code
Fault code
V
4A
520
V
4U
521
V
4U
522
V
4Y
523
V
4U
524
Table 22 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 – 6 720 647 367 (2012/11)
Cause
Description
Boiler safety temperature
The flow temperature
limiter (STB).
has reached 200 °F
(93 °C) (cut-out
temperature of boiler
temperature limiter).
Temperature difference at
Temperature difference
twin boiler sensor too great.
between flow
temperature sensors 1
and 2 too great
(divergence of > 9 °F/2s;
5 K/2s).
Short circuit between boiler
A fault has been
sensors 1 and 2.
detected in temperature
sensor test mode.
Circuit break on flow
Temperature at flow
temperature sensor.
temperature sensor.
< 23 °F (< -5 °C)
Flow temperature sensor
Current supply
short circuit.
temperature
> 266 °F (> 130 °C)
Troubleshooting
Testing sequence/
Cause
Measure
Fault can only occur as a
Check system
result of faults in system
configuration.
configuration (e.g. only
Check non-return valve
with 2-boiler systems).
direction of flow.
Check connectors on
Clean contacts/replace
boiler sensor and SAFe
connecting lead if
for dirt/damage.
necessary.
Check boiler sensor
If there are
resistance against sensor
discrepancies in
characteristic/visually
the sensor readings or
check temperature
the connector
sensor.
is defective, the
temperature sensor
Check boiler sensor
must be replaced.
voltage levels against
table (SAFe
Replace SAFe
documentation).
if there are
discrepancies.
Check sensor lead.
Replace if damaged.
Check connector.
If dirty, clean
or replace as necessary.
Check sensor readings
against sensor
If connector is loose,
characteristic.
reconnect properly.
Check temperature
Replace temperature
sensor voltage levels
sensor if there are
against table (SAFe
discrepancies.
documentation).
Replace SAFe
if there are
discrepancies.
Check sensor lead.
Replace if damaged.
Check connector.
If dirty, clean
or replace as necessary.
Check sensor readings
against sensor
If connector is loose,
characteristic.
reconnect properly.
Check temperature
Replace temperature
sensor voltage levels
sensor if there are
against table (SAFe
discrepancies.
documentation).
Replace SAFe if there
are discrepancies.
Check sensor lead.
Replace if damaged.
Check connector.
If dirty, clean or replace
Check sensor readings
as necessary.
against sensor
If connector is loose,
characteristic.
reconnect properly.
Check temperature
Replace temperature
sensor voltage levels
sensor if there are
against table (SAFe
discrepancies.
documentation).
Replace SAFe
if there are
discrepancies.
10
55