[9-05~9-08] Automatic setback function
Setback function provides the possibility to lower the water
temperature during space heating. The setback function can for
instance be activated during the night because the temperature
demands during night and day are not the same.
Remark that the b icon will be flashing during setback
operation. The calculated leaving water setback set
point is not shown during setback operation.
By default the setback function is disabled.
The setback function can be combined with the
automatic weather dependent set point operation.
Setback function is an automatic daily scheduled
function.
The setback function can be combined with the
schedule timer. When setback is active, the scheduled
space heating set point will be lowered with the [9-08]
leaving water setback value.
■ [9-05] Status: defines whether the setback function is turned
ON (1) or OFF (0)
■ [9-06] Start time: time at which setback is started
■ [9-07] Stop time: time at which setback is stopped
■ [9-08] Leaving water setback value
T
A
55°C
2°C [9-08]
B
53°C
[9-06]
A
Normal leaving water temperature set point or calculated
weather depended set point
B
Calculated leaving water setback temperature set point
t
Time
T
Temperature
It is advised to set the start time of automatic storage during night
[6-04] on the moment that the setback function starts [9-06].
Pay attention not to set the setback value too low,
especially during colder periods (e.g. winter time). It is
possible that the room temperature can not be reached (or
it will take a much longer time) because of the big
temperature difference.
[C] Setup on EKRP1HB digital I/O PCB
Solar priority mode
■ [C-00] Solar priority mode setting: for information concerning the
EKSOLHW solar kit, refer to the installation manual of that kit.
EKHVH/X008BB6V3 + EKHVH/X008BB6+9WN
Daikin Altherma indoor unit
4PW64330-1 – 07.2010
t
[9-07]
[D] Local shift value weather dependent
Local shift value weather dependent
The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting
dependent set point (heating operation only)" on page
selected.
■ [D-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
T
t
[1-02]
L
R
[1-03]
[1-00]
0°C
[1-01]
T
Target water temperature
t
T
Outdoor temperature
A
R
Range
L
Local shift value
[1-00], [1-01],
Applicable field setting of the weather dependent set
[1-02], [1-03]
point [1]
Outdoor temperature range (T
[D-03]
0
1
–2°C~2°C
2
3
–4°C~4°C
4
[E] Unit information readout
■ [E-00] Readout of the software version (example: 23)
■ [E-01] Readout of the EEPROM version (example: 23)
■ [E-02] Readout of the unit model identification (example: 11)
■ [E-03] Readout of the liquid refrigerant temperature
■ [E-04] Readout of the inlet water temperature
[E-03] and [E-04] readouts are not permanently
refreshed. Temperature readouts are updated after
looping through the field setting first codes again only.
"[1] Weather
13) is
T
A
)
Local shift value
A
2
4
2
4
Operation manual