[6] Domestic hot water storage and reheat operation
The storage and reheat domestic hot water will only be
carried out when the heating of the domestic hot water is
enabled by the
w
button.
Scheduled domestic hot water storage
The storage setpoint can be accessed directly using the
wj
buttons.
[6-03] Scheduled storage: defines whether the scheduled
domestic water heating storage during night is enabled (1) or
not (0).
[6-04] Scheduled storage start time: time of the night at which
the domestic water should be heated.
Selecting powerful domestic water heating operation
1
Press
v
for 5 seconds to activate powerful domestic water
heating operation.
Icons
w
and
)
start flashing.
Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.
Scheduled/continuous domestic hot water reheat
[6-05] Reheat: defines whether the scheduled domestic water
reheat during daytime is enabled (1) or continuous reheat is
enabled (2) or reheat is disabled (0)
[6-06] Scheduled reheat start time: time of the day at which the
domestic water should be heated.
[6-07] Domestic hot water reheat sepoint
[6-08] Domestic hot water reheat sepoint hysteresis
Example 1: Scheduled storage [6-03]=1, scheduled reheat [6-05]=1,
disinfection function [2-01]=1 activated.
T
A
B
[2-03]
Tdhw
[6-07]
[6-04]
[6-06]
[2-02]
A
Scheduled storage operation: activated at [6-04], heat up
domestic hot water untill domestic hot water user interface set
point Tdhw (e.g 55°C) is reached.
B
Scheduled reheat operation: activated at [6-06], heat up
domestic hot water untill domestic hot water reheat set point
[6-07] (e.g 45°C ) is reached.
C
Disinfection operation (if activated): activated at [2-02], heat up
domestic hot water untill domestic hot water disinfection set point
[2-03] (e.g 60°C) is reached. Refer to
on page
14.
t
Time
T
Domestic hot water temperature
Tdhw
Domestic hot water user interface set point
Operation manual
15
wi
and
C
t
"[2] Disinfection function"
Example 2: Scheduled storage [6-03]=1, continuous reheat [6-05]=2,
disinfection function [2-01]=1 activated.
T
A
B
[2-03]
Tdhw
[6-07]
[6-04]
A
Scheduled storage operation: activated at [6-04], heat up
domestic water till domestic hot water user interface setpoint
Tdhw (e.g 55°C), is reached.
B
Continuous reheat operation: continues activated heat up
domestic water till domestic hot water reheat set point [6-07] (e.g
45°C) is reached with a hysteresis of [6-08].
C
Disinfection operation (if activated): activated at [2-02] ,heat up
domestic water till domestic hot water disinfection set point [2-03]
(e.g 60°C) is reached. Refer to
page
14.
t
Time
T
Domestic hot water temperature
Tdhw
Domestic hot water user interface set point
Make sure the domestic water is only heated up to the
domestic hot water temperature you require.
Start with a low domestic hot water storage
temperature set point, and only increase if you feel
that the domestic hot water supply temperature is not
sufficient for your needs (this depends on your water
using pattern).
Make sure the domestic water is not heated
unnecessary. Start with activating automatic storage
during night (default setting). If it seems that the
domestic hot water night storage operation is not
sufficient for your needs, an additional scheduled
reheat during daytime can be set.
[9] Heating and cooling set point ranges
The purpose of this field setting is to prevent the user from selecting a
wrong (i.e., too hot or too cold) leaving water temperature. Thereto
the heating temperature set point range and the cooling temperature
set point range available to the user can be configured.
CAUTION
In case of a floor heating application, it is important to
limit the maximum leaving water temperature at
heating operation according to the specifications of
the floor heating installation.
In case of a floor cooling application, it is important to
limit the minimum leaving water temperature at
cooling operation (field setting of parameter [9-03]) to
16~18°C to prevent condensation on the floor.
■ [9-00] Heating set point upper limit: maximum leaving water
temperature for heating operation.
■ [9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.
■ [9-02] Cooling set point upper limit: maximum leaving water
temperature for cooling operation.
■ [9-03] Cooling set point lower limit: minimum leaving water
temperature for cooling operation.
C
B
[2-02]
"[2] Disinfection function" on
EKHVH/X008BB6V3 + EKHVH/X008BB6+9WN
Daikin Altherma indoor unit
4PW64330-1 – 07.2010