Field Settings; Procedure - Daikin EKHVH008BB6V3 Operation Manual

Altherma indoor unit
Hide thumbs Also See for EKHVH008BB6V3:
Table of Contents

Advertisement

5.
F
IELD SETTINGS
The default values mentioned in
page 17
are the values from factory. The actual initial
values shall be selected according to your application.
These values shall be confirmed by your installer.
CAUTION
The field settings [2] depends on the relevant local and
national regulations.
The field settings [9] depends on the application.
Before changing these settings, the new values shall be
confirmed by the installer and/or shall be according to the
local and national regulations.
The indoor unit shall be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. However, the field settings mentioned in
table" on page 17
can be modified to customer preferences. Thereto,
a number of so called field settings are available. These field settings
are accessible and programmable through the user interface on the
indoor unit.
Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under
settings table" on page
17. In this same list, we provided for 2
columns to register the date and value of altered field settings at
variance with the default value.
A detailed description of each field setting is given under
description" on page
13.
EKHVH/X008BB6V3 + EKHVH/X008BB6+9WN
Daikin Altherma indoor unit
4PW64330-1 – 07.2010
"Field settings table" on

"Field settings

"Field
"Detailed

5.1. Procedure

To change one or more field settings, proceed as follows.
3
2
Press the z button for a minimum of 5 seconds to enter FIELD
1
SET MODE.
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to
the right - (1).
Press the bgi button to select the appropriate field setting
2
first code.
Press the bgj button to select the appropriate field setting
3
second code.
Press the pfi button and pfj button to change
4
the set value of the select field setting.
5
Save the new value by pressing the pr button.
6
Repeat step 2 through 4 to change other field settings as
required.
When finished, press the z button to exit FIELD SET MODE.
7
Changes made to a specific field setting are only
stored when the pr button is pressed. Navigating to
a new field setting code or pressing the z button will
discard the change made.
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit
initialises itself.
Before shipping, the set values have been set as
shown under
"Field settings table" on page
1
17.