Adjust Temperature Rise

NOTE: Blower door must be installed when taking temperature
rise reading. Leaving blower door off will result in incorrect
temperature measurements.
CAUTION
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in shortened furnace
life.
Set air temperature rise within limits specified on the rating
plate to prevent reduced life of furnace components.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in overheating the
heat exchangers or condensing flue gases in heat
exchanger areas not designed for condensate.
Temperature rise must be within limits specified on unit
rating plate.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in component
damage.
Temperature rise must be within limits specified on furnace
rating plate. Recommended operation is at midpoint of rise
range or slightly above.
Place setup switch (TT) in ON position. Jumper R to W/W1 and
W2 to check highïgasïheat temperature rise. To check
lowïgasïheat temperature rise, remove jumper to W2.
Determine air temperature rise for both high and low gas heat.
Do not exceed temperature rise ranges specified on unit rating
plate for high and low gas heat.
This furnace must operate within the temperature rise ranges
specified on the furnace rating plate. Determine the air
temperature as follows:
a. Place duct thermometers in return and supply ducts
as close to furnace as possible. Be sure
thermometers do not "see" heat exchangers so that
radiant heat does not affect thermometer readings.
This is particularly important with straight run ducts.
b. When thermometer readings stabilize, subtract
returnïair temperature from supplyïair temperature to
determine temperature rise.
If the temperature rise is outside this range, check the
following:
a. Gas input for lowïand high gas heat operation.
b. Derate for altitude if applicable.
c. Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50ïin. w.c.
d. Adjust temperature rise by adjusting blower speed.
e. Increase blower speed to reduce temperature rise.
f. Decrease blower speed to increase temperature rise.
440 04 4321 02
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect 115V electrical power before changing speed
tap.
Table 3
COLOR
Gray
Yellow
Blue
Orange
Red
For lowïheat, the following connections can be made at
LOïHT on control:
a. Speed 2 (Orange)
b. Speed 1 (Red) ï Factory Setting
(Read following caution before changing taps).
UNIT DAMAGE HAZARD
To avoid operating outside the rise range and avoid
component damage:
1. NEVER connect Speed Tap 1 (Red) wire to "HI HT."
2. NEVER connect Speed Tap 2 (Orange) wire to "HI
HT" on all models.
To change blower motor speed selections for heating mode,
remove blower motor lead from control HIïHT terminal. (See
Figure 4) Select desired blower motor speed lead from one of
the other motor leads and relocate it to HIïHT terminal. (See
Table 3 for lead color identification.) Reconnect original lead on
SPARE terminal. Follow this same procedure for proper
selection of LOïHT and COOL speed selection.

Adjust Blower Off Delay (Heat Mode)

If desired, the main blower off time delay period may be
lengthened or shortened when operating in the heating mode
to provide greater comfort. For position of switches see
Figure 4 and Figure 15 for location of switches on control
center.
a. Remove blower door if installed.
b. Turn setup switches ON or OFF for desired blower off
c. Proceed to "Set Blower Off Delay" before installing
DESIRED HEATING MODE
BLOWER OFF DELAY

Adjust Cooling Airflow

The cooling airflow can be set from the remaining blower speed
taps. Refer to the Air Delivery Tables in these instructions.
If a two stage air conditioning or heat pump is installed, the Low
Cooling Speed is the same speed tap as the Lo Heat speed.
Specifications subject to change without notice.
Gas Furnace: (F/G)9MXT
WARNING
!
Blower Speed Taps
SPEED
FACTORY ATTACHED TO:
5
4
3
2
1
CAUTION
!
delay. See Table 4, Figure 4 and Figure 15.
blower door.
Table 4
Blower Speed Taps
SETUP SWITCH
(SW-2 & SW-3)
(SEC.)
SW-2
90
OFF
120
OFF
150
ON
180
ON
Cool
Spare
HI HT
Spare
LO HT/Cont. Fan
POSITION
SW-3
OFF
ON
OFF
ON
9