International comfort products F9MXT0401410A Service And Technical Support Manual page 13

Two stage, ecm blower motor 35” tall, high efficiency condensing gas furnace
Hide thumbs Also See for F9MXT0401410A:
Table of Contents

Advertisement

SERVICE AND TECHNICAL SUPPORT MANUAL
Figure 7
Typical TwoïStage Field Wiring Diagram
BLK
BLK
WHT
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
For an explanation of status codes, refer to service label
located on control door or Figure 14, and the troubleshooting
guide which can be obtained from your distributor.
Retrieving Stored Fault Codes
NOTE: Fault codes cannot be retrieved if a thermostat signal
(24-V on W, Y, G, etc.) is present, or if any delays such as
blower off-delays are active.
The stored status codes will NOT be erased from the control
memory when 115- or 24-V power is interrupted. See the
Service Label (See Figure 14) for more information. The most
recent fault code may be retrieved as follows:
1. Leave 115-V power connected to furnace.
2. Observe the status LED through the blower door (the
lower door on upflow applications) indicator. Refer to the
Service Label (See Figure 14) to interpret the LED.
3. Remove the Main/Control door (the upper door on upflow
installations).
4. BRIEFLY disconnect and reconnect ONE of the main
limit wires.
5. The LED will flash the last stored fault code. Refer to the
Service Label (See Figure 14) to interpret the LED.
6. A component test sequence will follow.
7. Reinstall the Main/Control door.
Component SelfïTest
NOTE:
The furnace control component test allows all
components to run for a short time; except the gas valve and
humidifier terminal HUM are not energized. The EAC-1 terminal
is energized when the blower is energized. The HUM terminal
is energized when the inducer is energized. This feature helps
diagnose a system problem in case of a component failure.
The component test feature will not operate if any thermostat
signal is present at the control and not until all time delays are
completed.
To begin Component SelfïTest:
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control.
3. Manually close blower door switch.
440 04 4321 02
NOTE 2
W
C
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
W2
COM
W/W1
NOTE 1
Y/Y2
JUNCTION
BOX
R
CONTROL
G
BOX
24-VOLT
TERMINAL
NOTES: 1.
BLOCK
FURNACE
Specifications subject to change without notice.
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
1-STAGE
THERMOSTAT
Y
R
G
TERMINALS
CONDENSING
UNIT
Connect Y/Y2-terminal as shown for proper operation.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
Caution must be taken when manually closing this switch for
service purposes.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, or death.
Blower access door switch opens 115ïV power to
control. No component operation can occur unless
switch is closed. Caution must be taken when
manually closing this switch for service purposes.
4. For approximately 2 sec, short (jumper) the C terminal on
control
to
the
quick-connect terminal on control until the LED goes off.
Remove jumper from terminals. (See Figure 4)
NOTE: If TEST/TWIN and C terminals are jumpered longer
than 2 sec., LED will flash code 10 and ignore component test
request.
Component test sequence is as follows:
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step g
of component test sequence.
c. After 7 seconds the hot surface igniter is energized for
15 sec., then off.
d. Blower motor operates on LOïHT speed for 10 sec.
e. Blower motor operates on HIïHT speed for 10 sec.
f. Blower motor operates on COOL speed for 10 sec.
Inducer motor goes to low speed for 10 sec., then
g.
stops.
5. Reconnect R lead to furnace control, remove tape from
blower door switch, and re-install blower door.
6. Verify furnace shut down by lowering thermostat setting
below room temperature.
7. Verify that furnace restarts by raising thermostat setting
above room temperature.
8. Release blower door switch, reattach wire to "R" terminal
on furnace control board and replace blower door.
Gas Furnace: (F/G)9MXT