Adjust Temperature Rise - International comfort products N9MSE0261408 Service And Technical Support Manual

Single stage, psc blower motor 35” tall, high efficiency condensing gas furnace
Table of Contents

Advertisement

SERVICE AND TECHNICAL SUPPORT MANUAL
Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate − 40,000 − 140,000 BTUH
Table 4 (CONT.)
Single Stage
(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE
RANGE
ft (m)
7001
(2134)
to
8000
(2438)
8001
(2439)
to
9000
(2743)
9001
(2744)
to
10000
(3048)
* Orifice numbers shown in BOLD are factory-installed.

Adjust Temperature Rise

NOTE: Blower door must be installed when taking temperature
rise reading. Leaving blower door off will result in incorrect
temperature measurements, due to possible changes in duct
static pressure and airflow.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in:
S
Overheating the heat exchangers or condensing
flue gases in heat exchanger areas not designed
for condensate
S
Shortened furnace life
S
Component damage
Temperature rise must be within limits specified on furnace
rating plate. Recommended operation is at midpoint of rise
range or slightly above.
Jumper R to W to check gas-heat temperature rise. Do not
exceed temperature rise ranges specified on unit rating plate.
This furnace must operate within the temperature rise ranges
specified on the furnace rating plate. Determine the air
temperature as follows:
1. Place duct thermometers in return and supply ducts as
close to furnace as possible. Be sure thermometers do
not "see" heat exchangers so that radiant heat does not
affect
thermometer
important with straight−run ducts.
2. When thermometer readings stabilize, subtract return−air
temperature from supply−air temperature to determine
temperature rise.
440 04 4402 07
SINGLE-STAGE FURNACE
A
V
G
.
G
A
S
HEAT VALUE
0.58
AT ALTITUDE
Orifice
Manifold
(Btu/cu ft)
No.
Pressure
650
42
675
43
700
43
725
44
750
44
775
44
800
44
825
44
625
42
650
43
675
43
700
44
725
44
750
44
775
44
600
42
625
43
650
43
675
44
700
44
725
44
readings.
This
is
particularly
Specifications subject to change without notice.
S
P
E
C
F I
C I
G
R
A
V
T I
Y
O
F
0.60
Orifice
Manifold
Orifice
No.
Pressure
No.
3.4
42
3.5
42
3.8
42
3.2
42
3.5
43
3.7
43
3.8
43
3.4
43
3.5
44
3.7
44
3.3
44
3.4
44
3.1
44
3.2
44
2.9
44
3.0
44
3.4
42
3.5
42
3.8
42
3.2
42
3.5
43
3.6
43
3.7
43
3.4
43
3.5
44
3.6
44
3.3
44
3.4
44
3.0
44
3.2
44
3.3
42
3.4
42
3.7
42
3.2
42
3.5
43
3.6
43
3.7
44
3.8
43
3.4
44
3.5
44
3.2
44
3.3
44
If the temperature rise is outside this range, check the
following:
1. Gas input rate.
2. Derate for altitude if applicable.
3. Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50−in. w.c. (125
Pa)
4. Adjust temperature rise by adjusting blower speed.
S
Increase blower speed to reduce temperature rise.
S
Decrease blower speed to increase temperature rise.
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect 115vac electrical power before changing speed
tap.
(Read following caution before changing taps.)
!
UNIT DAMAGE HAZARD
To avoid operating outside the rise range and avoid
component damage:
Refer to the Air Delivery Tables to determine which airflows
and settings are allowed for proper heating airflow. DO NOT
use the highlighted settings for heating airflow. The
highlighted settings are to be used for Cooling and
Continuous Fan ONLY.
Gas Furnace: N9MSE
N
A
T
U
R
A
L
G
A
S
0.62
0.64
Manifold
Orifice
Manifold
Pressure
No.
Pressure
3.6
42
3.7
3.3
42
3.4
3.8
42
3.2
3.5
43
3.6
3.8
43
3.4
3.5
44
3.7
3.3
44
3.4
3.1
44
3.2
3.6
42
3.7
3.3
42
3.4
3.7
42
3.2
3.5
43
3.6
3.7
44
3.8
3.5
44
3.6
3.3
44
3.4
3.6
42
3.7
3.3
42
3.4
3.7
43
3.8
3.4
43
3.5
3.7
44
3.8
3.4
44
3.5
WARNING
CAUTION
A11253B
13