When Using Wireless Remote Controller Instead Of Wired Remote Controller - Panasonic S-22ML1E5 Installation Instructions Manual

Vrf system air conditioner, refrigerant r410a
Table of Contents

Advertisement

<Cleaning the drain fi lter and drain pan>
Floor Standing Type (P1):
1.
Removing the front panel
Open the front panel with a lifting motion to detach the latch.
2.
Cleaning
Remove any dirt accumulated in the drain pan, and then
wipe it clean. Also, clean the drain filter in the same way as
the air filter.
(1) Push up
then
(2) Pull down
Front panel
Screw
Screw
Concealed Floor Standing Type (R1):
Remove the screws, open the front panel, and then remove any
dirt accumulated inside the drain pan and wipe it clean. Also,
clean the drain filter in the same way as the air filter.
Front panel
Screw
Drain pan
Drain filter
A
Latch
Side panel
B
Drain pan
Drain filter
How to adjust the air direction
1.
Remove the lid near the air discharge grille.
2.
Remove the 3 screws and the cover plate.
3.
Slide and lift up the air discharge grille.
4.
Rotate the blades of the grille to select in the desired air
discharge direction (90, 180 or 270 degrees).
5.
Return the cover plate and screw it in place. Then return
the lid to its original position.
Cover plate
4
3
■ When Using Wireless Remote Controller Instead
of Wired Remote Controller
Wall-Mounted (K1-Type)
When the wireless remote controller is to be used, slide the
switch (S011) on the indoor unit control PCB to the ON position.
● If this setting is not made, an alarm will occur.
(The operation lamp on the display blinks.)
Samples: S-22MK1E5, S-36MK1E5
Setting status
ON: Wireless: main, Wired: sub
OFF: Wired: main, Wireless: sub (at shipment)
Slide
43
2
1
Lid
Air discharge grille