Mounting - Panasonic S-22ML1E5 Installation Instructions Manual

Vrf system air conditioner, refrigerant r410a
Table of Contents

Advertisement

(6) Be sure to secure the wiring with the provided clamp.
NOT E
When closing the air intake grille, press the bottom right and left
corners and center. (Fig. 3-52)
Please refer to "How to replace the grille" for installing the air
intake grille.
WARNING
Loose wiring may cause the terminal to overheat or result
in unit malfunction. A fire hazard may also exist.
Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding
terminal, follow the instructions "How to connect wiring to the
terminal" and fasten the wire securely tight with the fixing screw
of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the wire about 8 mm. See the label
(Fig. 3-53) near the terminal plate.
For indoor unit
STRIP
SIZE
(2) Using a screwdriver, loosen the terminal screw on the
terminal plate.
(3) Insert the wire and tighten the terminal screw completely
using a screwdriver.
b) For Outdoor Unit
■ For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 25 mm.
(Fig. 3-54)
For outdoor unit
Solid wire
8 mm
(ACTUAL
SIZE)
Loop
Insulation
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using the pliers, bend the solid wire to form a loop suitable
for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal plate
and fix it securely with the removed terminal screw using a
screwdriver.
■ For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 10 mm and
tightly twist the wire ends. (Figs. 3-55 and 3-56)
Stranded wire
Fig. 3-52
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using a ring connector fastener or pliers, securely clamp
each stripped wire end with a ring connector. (Fig. 3-55)
(4) Place the ring connector wire, and replace and tighten the
removed terminal screw using a screwdriver. (Fig. 3-57)
Special
washer
Wire
Fig. 3-53

3-18. Mounting

(1) To install the indoor unit, mount the indoor unit onto the 2
tabs on the upper part of the rear plate.
(2) Hold down the air discharge outlet and press the lower part
of the indoor unit until it clicks to securely fasten to the 2
tabs on the lower part of the rear plate. (Fig. 3-58)
Fig. 3-54
16
Twist wire ends
Ring
connector
Fig. 3-55
Screw
Ring connector
Terminal plate
Wire
Push
Fig. 3-56
Screw and
special washer
Ring
connector
Fig. 3-57
Fig. 3-58