Temperature Rise Check - International comfort products N9MP1 Installation Instructions Manual

90+ single stage fan assisted, direct vent gas furnace
Hide thumbs Also See for N9MP1:
Table of Contents

Advertisement

Figure 51
Ignitor Location
1/
2
16
5
/
16
NOTE: Flame sensor has a different orientation in all 050 models.

Temperature Rise Check

The blower speed MUST be set to give the correct air temperature
rise through the furnace as marked on the rating plate. Tempera-
ture rise is the difference between supply and return air tempera-
tures.
To check temperature rise,use the following procedure:
1.
Place thermometers in supply and return air registers as
close to furnace as possible, avoiding direct radiant heat
from heat exchangers.
2.
Operate furnace continuously for 15 minutes with all regis-
ters and duct dampers open.
3.
Take reading and compare with range specified on rating
plate.
4.
If the correct amount of temperature rise is NOT obtained, it
may be necessary to change blower speed. A higher blower
speed will lower the temperature rise. A lower blower speed
will increase the temperature rise.
Changing Blower Speed
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to do so could result in death or personal
injury.
Turn OFF power to furnace before changing
speed taps.
NOTE: The speed taps that the manufacturer sets from the factory
for this product are based on a nominal 400 CFM per ton cooling
and the basic mid range on the temperature rise for heating.
Since the manufacturer cannot establish the static pressure
that will be applied to the unit, it is the responsibility of the in-
staller dealer/contractor to select the proper speed taps for the
application when the unit is installed.
42
!
REDUCED FURNACE LIFE HAZARD
Failure to properly set the air temperature rise may
1
/
4
result in reduced furnace life.
Use ONLY the following blower motor speed taps for
setting air temperature rise.
Blower Motor Speed Taps
Hi (BLK)
Med--Hi (O)
Med Lo (BL)
Lo (RED)
If it is necessary to change speeds, refer to steps below.
Table 12
* Med--High speed may not be provided on all models.
1.
2.
3.
Continuous- - Fan Operation using "G"
Energizing the "G" terminal on the furnace control provides contin-
uous fan operation. This is done by connecting the G terminal of
the thermostat to the G terminal on the furnace control. When the
FAN switch is turned from auto to ON the fan will operate continu-
ously at "HEAT" speed. EAC will be energized in this mode.
NOTE: In heating, the fan will turn off during furnace ignition and
warm up then restart at heating speed.
Hard Wired Continuous Fan Operation
A terminal is provided on the furnace control board located in the
circulating blower compartment for operation of the continuous fan
option. This connection is intended for the low speed motor tap,
and has a lower contact rating (8 amps) than the heat and cool
CAUTION
Blower Speed Chart
Wire Color
Black
Orange*
Blue
Red
Refer to Furnace Wiring Diagram for location of the heating
and cooling speed taps located on the furnace control as
well as location of unused blower motor speed leads. Use
the chart (Table 12) to determine the blower motor speed
settings.
Change the heat or cool blower motor speed by removing
the motor lead from the "Heat" or "Cool" terminal and re-
place it with the desired motor speed lead from the "Un-
used Motor Lead" location. Connect the wire previously
removed from the "Heat" or "Cool" terminal to the vacated
"Unused Motor Lead" terminal.
If the same speed must be used for both heating and cool-
ing, remove the undesired motor speed lead from the
"Heat" or "Cool" terminal and connect that lead to the open
terminal at "Unused Motor Lead" location. Attach a jumper
between the "Heat" and "Cool" terminals and the remaining
motor speed lead.
Note: For motors with (4) speed leads, it will be necessary to
tape off the terminal of the motor speed lead removed from
the "Heat" or "Cool" terminal with electrical tape since an
open terminal will not be available at the "Unused Motor
Lead" location.
Model Sizes
All
All
DO NOT USE
DO NOT USE
Motor Speed
High
Med--High
Medium
Low
440 01 1021 01